Specific Methods Of Creating ADFs
4200-002
88
Revision 6
NOTE:
The
Communications
status indicates
when it is
Downloading… the
data.
Figure 175. Hydrometer Data
Logger Interface
7.1.5 Capture Data Via IR
On the hydrometer module|data logger, press
the
/ON
button.
NOTE:
This process may be easier to do
if the data logger is disconnected
from the hydrometer.
Press
/
SEL
until the LED is flashing
FAST next to the desired string to select the
channel/string A-H from which data is to be
transferred.
Figure 176. Data
Logger Front View
NOTE:
The data logger LEDs indicate status as follows:
Fast
– A-H LED flashes fast: Channel has data and is
selected.
Steady
– LED is on: Channel has data but is not selected.
Slow
– LED flashes slowly: Channel is selected but has no
data.
Press
on the menu bar of the BAS software.