Vertiv™ NetSure™ IPE Series -48 VDC Outdoor Rectifier Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
49
2.6.4
Lashing of Cords and Cables
Follow all local laws and practices for installation requirements and clearances from power facilities. Installation must meet all
applicable laws, ordinances, rules, and codes.
All flexible power and signal cords attached to rectifier, battery and DC distribution boxes (if any), shall be lashed within 12”
(305mm) of the cord connection, so as not to transfer tension or pull on the physical connector termination or joint.
Connectors are IP65 rated when not accommodating installation cord or cable tension or pull.
At installation, use only approved outdoor rated devices and fittings, so as to protect all cords and cables from physical damage.
Installer to use appropriate cable strain relief fittings/brackets as locally approved for pole and/or wall mounting.
Cords and cables shall be lashed and supported at intervals not exceeding 6 ft (1000 mm).
Vertiv recommends a minimum cable bend radius of 6X of the cable diameter. Example: 20mm cable outer diameter, shall be
installed using a 6 x 20mm or 120mm inside bend radius, minimum.
Figure 2.49
Lashing of Cords and Cables
Radius= 6X of diameter of cable