Figure 1.5 Efficiency Curve (@ 220 VAC, 60 Hz)
1.5.3
Environmental Ratings
1.
Operating Ambient Temperature Range:
a)
-40 °C (-40 °F) to +55 °C (+131 °F) with full power performance.
b)
+55 °C (+131 °F) to +75 °C (+167 °F) with derating output.
c)
Output Regulation Temperature Coefficient: ±0.02% per degrees Celsius.
2.
Storage Ambient Temperature Range: -25 °C (-13 °F) to +55 °C (+131 °F).
3.
Relative Humidity: This rectifier is capable of operating in an ambient relative humidity range of 0% to 95%.
4.
Altitude: 3000 m (9842 feet). Derating operating ambient temperature range by 3 °C per 300 m above 3000 m.
5.
Surge Protection: EN61000-4-5 up to level 4, Telcordia GR-1089-Core issue 7:2017, IEEE C62.41-1999, B3.
AC Power Terminals:
Test Level
Source
Impedance
Performance
Criteria
Line to Line
Line to Ground
± 4 kV
± 4 kV
2 ohms
B
NA
± 6 kV
12 ohms
B
AC Power Port, Diff Mode and Common Mode (2 ohms impedance):
Minimum Peak
Voltage (volts)
Voltage Maximum
Rise/Minimum Decay
Time (
µ
s)
Minimum Peak
Current per
Conductor (amperes)
Current Maximum
Rise/Minimum Decay
Time (
µ
s)
Repetitions, each
Polarity
±
6000
1.2/50
3000
8/20
5
Criteria:
The EUT (Equipment Under Test) shall not be damaged and shall continue to operate properly after the
application of the first-level surge.
The rectifier will be designed to fulfill ANSI IEEE, C62.41-1999, B3.
The test wave is 1.2/50us and 8/20us mixed 6kV/3kA.
75.0
80.0
85.0
90.0
95.0
100.0
0
10
20
30
40
50
60
70
80
90 100
EF
FI
CI
EN
CY
%
Percent of Full Load
Efficiency Curve