Vertiv™ NetSure™ IPE Series -48 VDC Outdoor Rectifier Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
4
1.3.2
Customer Wiring Selection
Refer to Table 1.6 and Table 1.7.
Table 1.6 Customer Wiring Selection - China Market
P/N
Description
Usage
04119776
Cable set, 10m AC input cable.
AC input cable.
04119782
Cable set, 3m AC input cable.
04119779
Cable set, 3m DC power cable, rectifier to customer load,
1kW.
1kW DC load cable.
04119780
Cable set, 3m DC power cable, rectifier to customer load,
2kW.
2kW DC load cable.
04119783*
Cable set, 10m comm cable, rectifier to customer, DB15.
4 x DOs for customer use.
04119777
Cable set, 0.8m DC power cable, rectifier to battery, 2kW.
Battery to rectifier.
04119781*
Cable set, 0.8m comm cable, rectifier to battery, DB9.
RS 485 communication.
* The raw cable used is NOT CE marked.
Table 1.7 Customer Wiring Selection - EMEA Market
P/N
Description
Usage
RPM629065-10
IP65 QC RECTIFIER TO BATTERY 2X10 0.8M
Battery charge and discharge, power cable.
RPM629065-11
IP65 QC MAIN R RS485_2 CAN DI DB9 0.8M
Used for main rectifier under parallel mode
RPM629065-12
IP65 QC R-R DB9 CAN EXTN 0.8M
Used for CAN communication between
rectifiers under parallel installation ONLY.
RPM629065-14
IP65 QC MAIN R DB15 4DO RS485_1 2.5M
4 x DOs and a north bound RS485 for
customer use.
RPM629065-13
IP65 QC SINGLE R-BAT RS485 DB9 0.8M
Used for RS485 communication between
battery and rectifier. (for single rec
single battery ONLY!)
NOTE!
For 1kW load cables, 2kW load cable, and AC input cables:
For PG Gland Rectifier: Customer to provide raw DC and AC power cords and wire ferrules for termination into rectifier.
For Quick Connect Rectifier: Customer to use connectors supplied with rectifier, and supply ferrules and raw cords.
Customer to terminate wires in the field to the connectors furnished with the rectifier.