Temporary Operation
Installation Section
©Vertical Express
1-10
Printed in USA April 2020
Electronic Starter Setup
For Across the Line Motor Starting, see Mechanical Starter Set Up with ESP200 Overloads on page 1 - 11.
Electronic Starter Display
•
The electronic starter displays
MOTOR STATUS STOPPED
when the system is normal.
Reset the starter if it reads otherwise and, before continuing, correct any problem indi-
cated on the display.
•
The starter display reverts to
MOTOR STATUS STOPPED
after 5 minutes of inactivity.
1. Verify that the Starting Amps = the Motor Nameplate Amps x 3 (Mfg. default).
Optional: 2 x FLA = minimum setting, 4.5 x FLA = maximum setting.
2. From
the
MOTOR STATUS
menu, press
. The
STATUS
menu displays.
3. Press
twice to display the
PARAMETERS
menu.
4. From
the
PARAMETERS
menu, press
once.
STARTING AMPS
displays.
5. Set the starting amps value equal to three times the nameplate FLA.
a. Press
once to access the value.
b. Press
or
to adjust the value of the flashing digit. Press
to move to the
next digit.
c. Press
to exit the starting amps parameter.
A prompt to
ACCEPT
or
REJECT
the change displays. Press
to accept or
to reject
and correct the parameter.
EXIT MENU
OR SAVE
SCROLL DOWN
SCROLL UP
ENTER MENU
MOTOR STATUS
STOPPED
Summary of Contents for ICON 32
Page 1: ...Controller...
Page 3: ...INSTALLATION SECTION...
Page 4: ...INSTALLATION SECTION...
Page 39: ...ADJUSTMENT SECTION...
Page 40: ...ADJUSTMENT SECTION...
Page 83: ...DIAGNOSTICS SECTION...
Page 84: ...DIAGNOSTICS SECTION...
Page 131: ...TROUBLESHOOTING SECTION...
Page 132: ...TROUBLESHOOTING SECTION...
Page 165: ...SERVICE INFORMATION SECTION...
Page 166: ...SERVICE INFORMATION SECTION...
Page 205: ...REFERENCE SECTION SERVICE REFERENCE SECTION...
Page 206: ...REFERENCE SECTION...