DIAGNOSTICS
Vertical Express Product Manual
3-7
88500 v.1.0
Diagnostics Section
Adjustments
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
F18
—
1–3
Phase 1 Safety Edge Operation - This adjustment determines how the safety edge and
door operation interact during Fire Service Phase 1.
Operation. This adjustment must be coordinated with applicable Fire Codes.
Values:
1 = The safety edge is inhibited (no door re-open from the safety edge), and the doors
close at reduced door speed during Phase 1 Fire Service.
2 = The safety edge is inhibited (no door re-open from the safety edge), and the doors
close at normal door speed during Phase 1 Fire Service.
3 = The safety edge is functional (doors will re-open from the safety edge), and the doors
close at normal door speed during Phase 1 Fire Service.
F19
—
1–3
Phase 2 Safety Edge Operation - This adjustment determines how the safety edge and
door operation interact during Fire Service Phase 2.
Operation. This adjustment must be coordinated with applicable Fire Codes.
Values:
1 = The safety edge is inhibited (no door re-open from the safety edge), and the doors
close at reduced door speed during Phase 2 Fire Service.
2 = The safety edge is inhibited (no door re-open from the safety edge), and the doors
close at normal door speed during Phase 2 Fire Service.
3 = The safety edge is functional (doors will re-open from the safety edge), and the doors
close at normal door speed during Phase 2 Fire Service.
F20
—
0–1
Fire Lift - Use this adjustment to designate an elevator as a Fire Lift.
Note: This adjustment only applies to fire service types that require the
designation of Fire Lifts.
Values:
0 = The elevator is not designated as a Fire Lift.
1 = The elevator is designated as a Fire Lift.
F21
—
0–1
B44 Phase 2 Activation Location - Only use this adjustment for B44 Fire Service Operation.
Note
: This adjustment will determine whether Phase 2 Operation is allowed to activate/
deactivate only at the main return landing, or activate/deactivate at the main or alternate
return landing.
Values:
0 = Phase 2 can activate only at the main return landing.
1 = Phase 2 can activate/deactivate at main or the alternate return landing.
F23
—
0–1
This adjustment will set the 1998 B44 Fire Service, Phase 2 return door speed.
Note
: If F23=1, the door closes in response to the initial Phase 2 recall
activation done at nudging speed. This action occurs without regard to adjustment F19
(used to set up the safety edge operation and the door
closing speed during Phase 2). See also: D11, D19, D40, Z16.
Values:
0 = The doors close at a speed determined by the F19 adjustment.
1 = The doors close at nudging speed.
F24
—
0–1
This adjustment will set 2000 Fire Service (A17 & B44) Phase 2 recall floor.
Values:
0 = Phase 2 recall will take the car to the main fire floor.
1 = Phase 2 recall will take the car to the current active fire floor.
F25
—
0–1
This adjustment will set the Fire Service Return Indicator (Fire Hat).
Note
: The F25 setting has no effect on the 2004 Fire Service. The Fire Hat light will remain
active while either Phase 1 or Phase 2 is active.
Values:
0 = The Fire Hat light is active during Phase 1 Recall and, where applicable, during Phase
2 Recall. The light will deactivate when the car arrives at the fire floor.
1 = The Fire Hat light will remain active while Phase 1 or Phase 2 is active.
Adj
(cont.)
Unit
Range
Definition
(cont.)
Summary of Contents for ICON 32
Page 1: ...Controller...
Page 3: ...INSTALLATION SECTION...
Page 4: ...INSTALLATION SECTION...
Page 39: ...ADJUSTMENT SECTION...
Page 40: ...ADJUSTMENT SECTION...
Page 83: ...DIAGNOSTICS SECTION...
Page 84: ...DIAGNOSTICS SECTION...
Page 131: ...TROUBLESHOOTING SECTION...
Page 132: ...TROUBLESHOOTING SECTION...
Page 165: ...SERVICE INFORMATION SECTION...
Page 166: ...SERVICE INFORMATION SECTION...
Page 205: ...REFERENCE SECTION SERVICE REFERENCE SECTION...
Page 206: ...REFERENCE SECTION...