Adjustments
Diagnostics Section
©Vertical Express
3-16
Printed in USA April 2020
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
V26
—
0–2
VIP Calls Assigned by.
Values:
0 = Best Car
1 = Priority
2 = Preferred (Security or Kiosk)
X10
—
0–1
Audible Car Call Enable - This adjustment sets an audible signal to alert a handicapped
passenger that a car call has been accepted by the elevator.
Values:
0 = Disable
1 = Enable
X11
—
0–2
Arrow Type - This adjustment sets the direction and preference arrows.
Direction arrows indicate direction of actual car movement.
Preference arrows indicate direction in which car has a preference to run.
Values:
0 = Direction arrows
1 = Preference arrows
2 = Preference and direction arrows
X12
—
0–1
Car Lantern at Door Reversal Limit - This adjustment enables car lantern operation when
the door reaches the reversal limit switch.
Values:
0 = Disable
1 = Enable
X13
—
0–1
Car Lantern at Lobby - This adjustment enables car lantern operation when the car
reaches the lobby.
Values:
0 = Disable
1 = Enable
X14
0.1 sec.
1–48
Flasher Rate - This adjustment sets the flashing rate for the flashing jewels.
X15
—
0–4
Front Lantern Type - This adjustment sets the type of lanterns used for front openings.
Values:
0 = No Lanterns
1 = Car Lanterns only
2 = Hall Lanterns only
3 = Both Car and Hall Lanterns
4 = Arrival Lanterns
X16
0.1 sec.
0–40
Lantern Delay at Lobby - This adjustment sets the delay time of lantern activation at lobby.
X17
—
0–2
Lantern Fire Position - This adjustment sets when the lanterns activate during fire service.
Values:
0 = At slow-down
1 = At leveling zone
2 = At floor level
X18
0.1 sec.
0–20
Lantern Off Time - This adjustment sets the duty of the off time during on/off cycle of lan-
terns and gongs operation.
X19
0.1 sec.
0–20
Lantern On Time - This adjustment sets the duty of the on time during on/off cycle of lan-
terns and gongs operation.
X20
minutes
0–10
PI Timeout Time - This adjustment sets the time delay before the position indicators (PI)
will turn off (if allowed by other options that may be active).
Note
: If this value is not set, PI Timeout will not be allowed.
Adj
(cont.)
Unit
Range
Definition
(cont.)
Summary of Contents for ICON 32
Page 1: ...Controller...
Page 3: ...INSTALLATION SECTION...
Page 4: ...INSTALLATION SECTION...
Page 39: ...ADJUSTMENT SECTION...
Page 40: ...ADJUSTMENT SECTION...
Page 83: ...DIAGNOSTICS SECTION...
Page 84: ...DIAGNOSTICS SECTION...
Page 131: ...TROUBLESHOOTING SECTION...
Page 132: ...TROUBLESHOOTING SECTION...
Page 165: ...SERVICE INFORMATION SECTION...
Page 166: ...SERVICE INFORMATION SECTION...
Page 205: ...REFERENCE SECTION SERVICE REFERENCE SECTION...
Page 206: ...REFERENCE SECTION...