40
FP15 & FP15A Waterloo - Installation and Operation Manual
6.3.5.3
Option #3 - Installation on a more than 8" raised base
•
When installed on a more than 8
"
(203 mm) raised base
(C)
, A 2.00 R value for the hearth extension is
required. The non-combustible hearth extension floor area must extend at least 16" (406 mm)
(B)
in
front of the hearth.
•
The joint between the hearth extension and the fireplace
(E)
, for the entire width of the floor
protection, must be protected by a bent and continuous piece of sheet metal (not included).
•
An 84" clearance between the fireplace base and the ceiling
(A)
must be respected.
MINIMUM MEASUREMENTS
A
84" (2134 mm)
B
16" (406mm)
C
More than 8" (203 mm)
E
2" (51 mm)
Summary of Contents for Waterloo FP15
Page 10: ...10 FP15 FP15A Waterloo Installation and Operation Manual 2 3 Measurements FP15 ...
Page 11: ...FP15 FP15A Waterloo Installation and Operation Manual 11 ...
Page 12: ...12 FP15 FP15A Waterloo Installation and Operation Manual 2 4 Measurements FP15A ...
Page 13: ...FP15 FP15A Waterloo Installation and Operation Manual 13 ...
Page 77: ...FP15 FP15A Waterloo Installation and Operation Manual 77 ...
Page 87: ...NOTES ...
Page 88: ...88 FP15 FP15A Waterloo Installation and Operation Manual ...
Page 89: ......