tected by connecting the release or relay in series with 

the phase windings. Selection and adjustment of the 

releases must be based on the rated value of the phase 

current (x0.58 rated current of the motor). If such a 

connection is not possible, suitable protection switches 

must be used, for example with phase failure control. 

For polechanging motors current-dependent delayed re-

leases or relays have to be provided for each rotational 

speed level that can be locked against each other.

For type of protection increased safety “e” 

(“eb”) the starting will be controlled as well. 

Therefore the protection device must switch 

off within the time period t

E

 that is given for 

the corresponding temperature class when 

the rotor is blocked. The requirement is 

fulfilled if the release time (it can be taken 

from the release characteristics (starting 

temperature 20°C) for the ratio I

A

/I

N

) is not 

higher than the indicated t

E

 time.

Electrical machines of type of protection increased  

safety “e” (“eb”) for heavy starting (start-up time >  

1,7 x t

E

 time) must be protected by a starting control  

according to the information of the certificate of confor-

mity. They have to be certified accordingly. 

Thermal motor protection by means of direct 

temperature monitoring of the winding is 

permissible if this is certified and indicated 

on the name plate. The protection consists 

of thermo couples according to DIN 44081/ 

44082 that ensures explosion protection 

together with a tripping device with type of 

protection marking 

 II (2) G. For pole-

changing motors it is necessary to have 

separate protection devices for each rotation 

speed level, that can be locked against each 

other. 

Auxiliary devices

Explosion-protected motors can be equipped with diffe-

rent auxiliary devices as option:

Additional thermal motor protection

For monitoring the stator winding temperature it is pos-

sible to have thermo couples installed in the motor (PTC 

thermistors, KTY or PT100). For their connection suita-

ble auxiliary clamps for auxiliary circuits are available 

in the main terminal box or in additional terminal boxes. 

The connection is done according to the attached 

connection diagram. 

Thermal motor protection as inherent protection

The use of thermal winding protection as inherent motor 

protection is only permissible if the operation is tested 

separately and certified by a notified body. On the name 

plate instead of the t

E

 time a t

A

 time is marked.  

In addition the following text will be printed on the name 

plate: “operation only with tested PTC tripping device 

and marking 

 II (2) G”.

“Do only operate with approved PTC-Ther-

mistor-Relays with indication 

 II (2) G”.

Anti-condensation heating

The heating tapes must comply with the directive 

2014/34/EU (RL94/9/EC). The heating power and the 

input supply voltage are indicated on the name plate 

of the motor. For their connection either in the main 

terminal box or in the auxiliary terminal boxes suitable 

clamps for auxiliary circuits are provided. The connec-

tion is done according to the attached connection dia-

gram. The anti-condensation heating has to be switched 

on only after disconnection of the motor. It shall not be 

switched on while the motor is in operation. 

Forced ventilation unit

The fans must comply with the directive 2014/34/EU 

(RL94/9/EC). The forced ventilation unit is dissipating 

the lost heat at operation of the main motor. During 

operation of the main motor the motor of the forced 

ventilation unit has to be switched on. After discon-

nection of the main motor the forced ventilation has to 

continue depending on the temperature. For motors with 

forced ventilation units that are dependent of the sense 

of rotation, the sense of rotation has to be observed 

unconditionally (see rotation mark). Only manufacturer 

approved forced ventilation units shall be used. The 

forced ventilation unit has to be connected according 

to the connection diagram that is supplied inside of the 

terminal box. 

Special design for terminal box on N-side 

The terminal box for this special design is located on 

N-side of the motor before the fan cover. To realise this 

design the stator housing was turned during production. 

Special marking for type designation: 

KNS… 

 for sizes 56 to 132..T  

(VEM motors Thurm GmbH) 

KN … 

 for sizes 112 to 400 (VEM motors GmbH)

For motors of category 2 a special approval is neces-

sary. 

Fitting with RFID transponder (Memory motor)

As option it is possible to equip the motor with an RFID 

transponder (TAG). This feature is called memory motor, 

marked with “MM” according to factory standard  

EW-N 1002, page 13. The transponder D14-TAGspecial 

ATEX (RFID System iID®2000, 13.56 MHz based on 

ISO 15693 is used. 

 The reading of the data may be carried out in 

areas with an explosive atmosphere only 

with a reader approved in accordance with 

Directive RL 2014/34/EU (Directive 94/9/EC).

External heat and cooling sources

No extra measures will be necessary for existing exter-

nal heat and cooling sources, if the temperatures at the 

installation site are not exceeded. If the temperatures 

are exceeded or impacts on operational temperatures 

or maximum surface temperatures can be expected 

provisions will have to be made to maintain and confirm 

explosion protection. If in doubt please contact the 

manufacturer.

Summary of Contents for K11 Series

Page 1: ...EX ATEX ATEX Additional Installation Operating and Maintenance Instructions Explosion protected three phase asynchronous motors with squirrel cage rotor for low voltage Ident Nr 50229 01 Version 08 20...

Page 2: ...ark IE is added to the type designation whereas 1 2 3 acc to IEC EN 60034 30 1 Example IE3 K11R 132S 4 Ex e IIC T3 Type of protection increased safety e eb Type of protection n increased safety ec Typ...

Page 3: ...zones 1 and 2 at least IP 55 for operation in zone 22 and IP 65 for operation in zones 21 and 22 with conducting dust For combinations always the highest required type of protection has to be used The...

Page 4: ...urface enclosure shaft Motors with double identification are only intended for use in gas or dust explosive atmospheres Use in hybrid mixtures must be checked and approved separately Generally notes f...

Page 5: ...60034 30 1 is allowed for explosion protected motors Indicated are IE class and rated efficiency The determination of the motor efficiency is done with direct measurement complying with IEC EN 60034 2...

Page 6: ...ection the standard security and starting instructions are valid The cable glands or screwed sealing plugs must be admitted for use in Exapplications The installation torques sealing areas and clamp r...

Page 7: ...300 Stud screw terminal M16M12 M8 1000 A VEM KLP 1000 1000 70 2 x 240 Current rail M10 K1X 200 A KM 10 8 VEM 10 8 100 70 Stud saddle terminal M8 2 x M6 K2X 200 A KM 10 8 VEM 10 8 100 70 Stud saddle t...

Page 8: ...wing of holes 3 The inner earth conductor from the motor green yellow with crimped lug has to be placed under the clamping yoke of the earth connection 4 The outgoing cables of the motor have to be so...

Page 9: ...ted PTC tripping device and marking II 2 G Do only operate with approved PTC Ther mistor Relays with indication II 2 G Anti condensation heating The heating tapes must comply with the directive 2014 3...

Page 10: ...t free room if possible If this is not possible suitable measures have to be taken to prohibit that dust can collect inside of the enclosure At disassembly take extra care that the sealing parts like...

Page 11: ...th life time lubrication From size 315MX upwards they are equipped with relubrica tion devices which can be ordered for smaller motors as option Information about bearings and relubrication can be fou...

Page 12: ...einforced bearings are supplied with a transportation safety device The transportation safety device at the shaft end must only be removed during installation of the motor and before switching on Turn...

Page 13: ...x 1 5 50 612 M1 EX 3 6 5 14 5 M 16 x 1 5 50 616 M EX 5 9 17 5 M 20 x 1 5 50 620 M1 EX 6 12 22 7 5 M 20 x 1 5 50 620 M EX 9 13 22 7 5 M 25 x 1 5 50 625 M EX 11 16 27 10 M 32 x 1 5 50 632 M EX 14 21 34...

Page 14: ...14 08 2017 50229 01 EU Declaration of Conformity according to EU Directive 2014 34 EU...

Page 15: ...b IIIC TX C Db 0637 II 2G II 2D Ex db IIC T3 T6 or Ex db IIC T3 T6 Gb or Ex d IIC T3 T6 or Ex d IIC T3 T6 Gb or optionally Ex tb IIIC T200 C T85 C Db 0637 II 2G II 2D Ex db eb IIC T3 T6 or Ex db eb II...

Page 16: ...roup com High voltage department Fon 49 351 208 3237 Fax 49 351 208 1108 E mail high voltage vem group com Drive systems department Fon 49 351 208 1154 Fax 49 351 208 1185 E mail drive systems vem gro...

Reviews: