Hints for screwed cable glands that are admitted for 

explosion protection 

The terminal boxes are designed as standard with 

metric threaded holes according to EN 50262 or on 

request with NPT-threaded holes according to ANSI 

B1.20.1-1983. At delivery the holes are closed with 

plugs or ATEX-certified cable glands. For connection 

of the motor only use cable entries that are designed 

according to directive 2014/34/EU (RL94/9/EC) and 

have at least IP 55 type of protection. 

For motors in type of protection flameproof enclosure “t” 

(IP 6X necessary!) the cable entries and plugs must be 

designed according to directive 2014/34/EU (RL94/9/EC) 

(ATEX) and have at least IP 65 type of protection.

All unused cable entry points must be closed 

with plugs according to the minimum type of 

protection listed in directive 2014/34/EU 

(RL94/9/EC) (ATEX). Existing plugs must be 

checked accordingly and if necessary they 

have to be changed.

The specification of thread type is given on the 

equipment (name plate or terminal box). Alternatively 

the instruction about cable entry thread, number and 

position of cable entries can be given in the dimensional 

drawing of the motor. For explosion protected VEM-

motors cable glands of the company Jacob are used, if 

not ordered otherwise. The following specifications must 

be observed for these special cable glands: 

Thread

Part-No.

For cable diameter 

[mm]

Width across flats 

[mm]

Installation torque 

[Nm]

M 12 x 1.5

50.612 M/EX

3...6

14

5

M 12 x 1.5

50.612 M1/EX

3...6.5

14

5

M 16 x 1.5

50.616 M/EX

5...9

17

5

M 20 x 1.5

50.620 M1/EX

6...12

22

7.5

M 20 x 1.5

50.620 M/EX

9...13

22

7.5

M 25 x 1.5

50.625 M/EX

11...16

27

10

M 32 x 1.5

50.632 M/EX

14...21

34

15

M 40 x 1.5

50.640 M/EX

19...27

43

20

M 50 x 1.5

50.650 M/EX

24...35

55

20

M 63 x 1.5

50.663 M/EX

32...42

65

20

M 63 x 1.5

50.663 M1/EX

40...48

65

20

M 75 x 1.5*)

HAWKE International

54.5...65.3

95

20

M 80 x 1.5*)

HAWKE International

67...73

106.4

20

M 90 x 1.5*)

HAWKE International

67…77.6

115

20

M 100 x 1.5*)

HAWKE International

75…91.6

127

20

*) Baseefa06ATEX0056X or IEC BAS 06.0013X.

Ex-EMC-brass screw connection, metric thread, EC declaration of conformity DMT 99 ATEX E 016

Thread

Part-No.

For cable diameter 

[mm]

Width across flats 

[mm]

Installation torque 

[Nm]

M 12 x 1.5

50.612 M/EMV/EX

3...6

14

5

M 12 x 1.5

50.612 M1/EMV/EX

3...6.5

14

5

M 16 x 1.5

50.616 M/EMV/EX

5...9

17

5

M 20 x 1.5

50.620 M1/EMV/EX

6...12

22

7.5

M 20 x 1.5

50.620 M/EMVEX

9...13

22

7.5

M 25 x 1.5

50.625 M/EMV/EX

11...16

27

10

M 32 x 1.5

50.632 M/EMV/EX

14...21

34

15

M 40 x 1.5

50.640 M/EMV/EX

19...27

43

20

M 50 x 1.5

50.650 M/EMV/EX

24...35

55

20

M 63 x 1.5

50.663 M/EMV/EX

32...42

65

20

M 63 x 1.5

50.663 M1/EMV/EX

40...48

65

20

M 75 x 1.5*)

HAWKE International

54.5...65.3

95

20

M 80 x 1.5*)

HAWKE International

67...73

106.4

20

M 90 x 1.5*)

HAWKE International

67…77.6

115

20

M 100 x 1.5*)

HAWKE International

75…91.6

127

20

*)

 Baseefa06ATEX0056X or IEC BAS 06.0013X.

Ex-brass screw connection, metric thread, EC declaration of conformity DMT 99 ATEX E 016

If screwed cable glands or plugs according to directive 

2014/34/EU (RL94/9/EC) (ATEX) from other manu-

facturers are used please observe the corresponding 

manufacturers information.

Summary of Contents for K11 Series

Page 1: ...EX ATEX ATEX Additional Installation Operating and Maintenance Instructions Explosion protected three phase asynchronous motors with squirrel cage rotor for low voltage Ident Nr 50229 01 Version 08 20...

Page 2: ...ark IE is added to the type designation whereas 1 2 3 acc to IEC EN 60034 30 1 Example IE3 K11R 132S 4 Ex e IIC T3 Type of protection increased safety e eb Type of protection n increased safety ec Typ...

Page 3: ...zones 1 and 2 at least IP 55 for operation in zone 22 and IP 65 for operation in zones 21 and 22 with conducting dust For combinations always the highest required type of protection has to be used The...

Page 4: ...urface enclosure shaft Motors with double identification are only intended for use in gas or dust explosive atmospheres Use in hybrid mixtures must be checked and approved separately Generally notes f...

Page 5: ...60034 30 1 is allowed for explosion protected motors Indicated are IE class and rated efficiency The determination of the motor efficiency is done with direct measurement complying with IEC EN 60034 2...

Page 6: ...ection the standard security and starting instructions are valid The cable glands or screwed sealing plugs must be admitted for use in Exapplications The installation torques sealing areas and clamp r...

Page 7: ...300 Stud screw terminal M16M12 M8 1000 A VEM KLP 1000 1000 70 2 x 240 Current rail M10 K1X 200 A KM 10 8 VEM 10 8 100 70 Stud saddle terminal M8 2 x M6 K2X 200 A KM 10 8 VEM 10 8 100 70 Stud saddle t...

Page 8: ...wing of holes 3 The inner earth conductor from the motor green yellow with crimped lug has to be placed under the clamping yoke of the earth connection 4 The outgoing cables of the motor have to be so...

Page 9: ...ted PTC tripping device and marking II 2 G Do only operate with approved PTC Ther mistor Relays with indication II 2 G Anti condensation heating The heating tapes must comply with the directive 2014 3...

Page 10: ...t free room if possible If this is not possible suitable measures have to be taken to prohibit that dust can collect inside of the enclosure At disassembly take extra care that the sealing parts like...

Page 11: ...th life time lubrication From size 315MX upwards they are equipped with relubrica tion devices which can be ordered for smaller motors as option Information about bearings and relubrication can be fou...

Page 12: ...einforced bearings are supplied with a transportation safety device The transportation safety device at the shaft end must only be removed during installation of the motor and before switching on Turn...

Page 13: ...x 1 5 50 612 M1 EX 3 6 5 14 5 M 16 x 1 5 50 616 M EX 5 9 17 5 M 20 x 1 5 50 620 M1 EX 6 12 22 7 5 M 20 x 1 5 50 620 M EX 9 13 22 7 5 M 25 x 1 5 50 625 M EX 11 16 27 10 M 32 x 1 5 50 632 M EX 14 21 34...

Page 14: ...14 08 2017 50229 01 EU Declaration of Conformity according to EU Directive 2014 34 EU...

Page 15: ...b IIIC TX C Db 0637 II 2G II 2D Ex db IIC T3 T6 or Ex db IIC T3 T6 Gb or Ex d IIC T3 T6 or Ex d IIC T3 T6 Gb or optionally Ex tb IIIC T200 C T85 C Db 0637 II 2G II 2D Ex db eb IIC T3 T6 or Ex db eb II...

Page 16: ...roup com High voltage department Fon 49 351 208 3237 Fax 49 351 208 1108 E mail high voltage vem group com Drive systems department Fon 49 351 208 1154 Fax 49 351 208 1185 E mail drive systems vem gro...

Reviews: