background image

 

 

                         
www.velocitydetection.com                        Doc:   GLT-311-7-1                      Issue: 001                              Date: 28/10/2020

 

 

VDOT-U5015 Explosion Proof Smoke Detector 

PROTECTION AGAINST MOISTURE DAMAGE 

 

It is important to take proper precautions during installation to 
ensure that moisture will not come in contact with the electrical 
connections of the system. The integrity of the system regarding 
moisture protection must be maintained for proper operation and is 
the responsibility of the installer.  
 
If conduit is used, the use of proper conduit installation techniques, 
breathers, glands, and seals is required to prevent water ingress 
and/or maintain the explosion-proof rating.  
 
Conduit drains must be installed at water collection points to 
automatically drain accumulated moisture. Conduit breathers 
should be installed at upper locations to provide ventilation and 
allow water vapor to escape. At least one breather should be used 
with each drain.  
 
Conduit raceways should be inclined so that water will flow to low 
points for drainage and will not collect inside enclosures or on 
conduit seals. If this is not possible, install conduit drains above the 
seals to prevent the collection of water or install a drain loop below 
the detector with a conduit drain at the lowest point of the loop. 
 

POWER SUPPLY REQUIREMENTS 

 

Calculate the total detection system power consumption rate in 
watts from cold start-up. Select a power supply with adequate 
capability for the calculated load. Ensure that the selected power 
supply provides sufficient regulated and filtered output power for 
the entire system. If a back-up power system is required, a 
float-type battery charging system is recommended. If an existing 
source of power is being used, verify that system requirements are 
met.  
 

TRANSPORT COVER 

 

The Transport Cover (see Figure 4) keeps dust and particles out of 
the smoke chamber that may enter during transport, handling, or 
installation. It should remain fastened on the detector through the 
installation process.  
 

IMPORTANT 

 

Remove the cover 

only 

after installation is complete and prior to 

powering the detector for the first time. 
 

 

 

 

MOUNTING LOCATION OPTIONS 

 

Ceiling Mount 

 

The U5015 is intended for surface mounting. It is normally mounted 
on the ceiling no less than six inches from a side wall (See Figure 5). 
The exact location of the detector must be determined by an 
evaluation based on engineering judgement, or if possible, by field 
tests. 

       

 

Wall Mount 

 

The  U5015  can  also  be  mounted  on  a  side  wall  (See  Figure  6).  The 
exact location of the detector must be determined by an evaluation 
based on supplemented engineering judgement, or if possible, by  
field tests.  

IMPORTANT

 

Whenever possible, select a mounting orientation where the LED is 
visible to personnel within the area. 
 

                         

 

 

MOUNT THE DETECTOR 

 

Using three No. 8 flat head screws (or equivalent) placed through 
the counter bored holes in the detector flange, secure the detector 
junction box to the surface location. 
 

WIRING CABLE REQUIREMENTS 

 

Always use proper temperature rated cabling type and diameter for 
input power as well as output signal wiring. 14 to 18 AWG shielded 
stranded copper wire is recommended. 
 

Summary of Contents for SmokeWatch VDOT-U5015

Page 1: ...essing plants Petroleum refineries Turbine enclosures Battery rooms HVAC applications The hot swappable sensor module is intrinsically safe and allows live maintenance while under power without de cla...

Page 2: ...om 12 17 9 Vdc 500 ohms from 18 to 19 9 Vdc and 600 ohms from 20 30 Vdc TERMINALS UL CSA rated for 14 18 AWG or 2 5 0 75 mm2 wire THREAD OPTIONS 3 4 inch NPT or M25 Multi port models available ENCLOSU...

Page 3: ...status LATCHING A detector configured for latching operation will remain in an alarm state indefinitely after an alarm occurs NON LATCHING A detector configured for non latching operation will check...

Page 4: ...t be installed in areas in which Ammonia Hydrogen Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each...

Page 5: ...ected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float type battery charging system is recommended If an existin...

Page 6: ...2 to 15 for wiring examples WIRING PROCEDURE Ensure that all cables are terminated properly Conductor insulation should be stripped off with a bare conductor length of 0 2 inch 5 mm minimum and 0 7 in...

Page 7: ...g compartment is the only part of the smoke detector that should be opened by the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke...

Page 8: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 9: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 10: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 11: ...t the Velocity Detection office so that a Return Material Authorization RMA number can be assigned A written statement describing the malfunction must accompany the returned device or component to ass...

Page 12: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 13: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 14: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 15: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Reviews: