background image

 

 

                         
www.velocitydetection.com                        Doc:   GLT-311-7-1                      Issue: 001                              Date: 28/10/2020

 

 

VDOT-U5015 Explosion Proof Smoke Detector 

The smoke alarm relay has a single set of terminals and normally 
open / normally closed contacts, and normally de-energized 
operation.  
 
The fault relay has a single set of terminals and normally open 
contacts, and normally energized operation.  
 
The auxiliary relay has a single set of terminals and normally open / 
normally closed contacts, and normally de-energized operation.

 

 

IMPORTANT 

 

             The auxiliary relay functions as pre-alarm.  

 

0 to 20 mA Output 

 

The U5015 provides a 0 to 20 mA dc current for transmitting 
detector status information to other devices. The circuit is wired in a 
non-isolated configuration and can drive a maximum loop resistance 
of 300 ohms from 12 to 17.9 Vdc, 500 ohms from 18 to 19.9 Vdc, 
and 600 ohms from 20 to 30 Vdc. Table 1 defines the current levels 
and corresponding detector status. The output is calibrated at the 
factory, with no need for field calibration. 
 

 

 

NOTE 
The output of the 0 to 20 mA current loop is monitored by the fault 
detection circuitry of the U5015. Therefore, an open circuit on the 
loop will cause the fault relay to change state.  
 

 

An alarm will normally over-ride a fault, unless the nature of the 
fault impairs the ability of the detector to generate or maintain an 
alarm output (i.e., loss of operating power). 
 
 

INTEGRAL WIRING COMPARTMENT 

 

All external wiring to the device is connected within the integral 
junction box. The detector is furnished with a maximum of four 
conduit entries, with either 3/4 inch NPT or M25 threads.  
 

LED 

 

An LED, located on the detector (see Figure 1), indicates normal 
operation and notifies personnel of an alarm. Table 2 indicates the 
condition of the LED for each status. 
 

LATCHING 

 

A detector configured for latching operation will remain in an alarm 
state indefinitely, after an alarm occurs.  
 

NON-LATCHING 

 

A detector configured for non-latching operation will check the alarm 
status of the detector once every 10 seconds. Once smoke falls below 
the  alarm  threshold,  the  alarm  annunciation  will  clear  within  10 
seconds.  

IMPORTANT 

 

The latching or non-latching configuration must be specified 
during order placement. 

 

It is 

not 

field configurable. 

 

 
Only the alarm annunciation can be configured for latching 
operation. 

 
 

CONTINUOUS SELF-TEST 

 

During  normal  operation,  the  detector  performs  the  Self-Test 
function automatically in the background once per second. During the 
test, detection is not interrupted and no indication is given if the test 
passed.  If  the  test  fails,  a  critical  fault  will  occur.  If  degradation  is 
present and approaching critical levels, an advisory fault will occur.  

 

MANUAL SELF-TEST 

 

The Manual Self-Test function will immediately check the smoke 
chamber optics for degradation. Once initiated, there will be a one 
second delay before the result of the check is active. If there is a 
failure, the LED will shut off immediately after the one second test 
and a critical fault will occur. If the test passes, an alarm will be 
annunciated while the LED remains active. 
 
For a latching detector, the alarm will continue until power is cycled 
to the unit. If the test passes, but there is degradation present and 
approaching  critical  levels,  an  advisory  fault  will  occur.  For  a  non-
latching detector the alarm will clear after 10 seconds.  

 

MAGNECTIC SWITCH

 

The magnetic switch is used to initiate the Manual Self-Test (see 
Figure 3). Apply the magnet to the exterior housing and the LED will 
light to indicate that the magnet is detected. The LED will remain lit 
for at least one second during the test. After the initial delay, the 
test status will be indicated as described in the "Manual Self-Test" 
section. 
                     

 

 
 

Summary of Contents for SmokeWatch VDOT-U5015

Page 1: ...essing plants Petroleum refineries Turbine enclosures Battery rooms HVAC applications The hot swappable sensor module is intrinsically safe and allows live maintenance while under power without de cla...

Page 2: ...om 12 17 9 Vdc 500 ohms from 18 to 19 9 Vdc and 600 ohms from 20 30 Vdc TERMINALS UL CSA rated for 14 18 AWG or 2 5 0 75 mm2 wire THREAD OPTIONS 3 4 inch NPT or M25 Multi port models available ENCLOSU...

Page 3: ...status LATCHING A detector configured for latching operation will remain in an alarm state indefinitely after an alarm occurs NON LATCHING A detector configured for non latching operation will check...

Page 4: ...t be installed in areas in which Ammonia Hydrogen Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each...

Page 5: ...ected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float type battery charging system is recommended If an existin...

Page 6: ...2 to 15 for wiring examples WIRING PROCEDURE Ensure that all cables are terminated properly Conductor insulation should be stripped off with a bare conductor length of 0 2 inch 5 mm minimum and 0 7 in...

Page 7: ...g compartment is the only part of the smoke detector that should be opened by the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke...

Page 8: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 9: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 10: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 11: ...t the Velocity Detection office so that a Return Material Authorization RMA number can be assigned A written statement describing the malfunction must accompany the returned device or component to ass...

Page 12: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 13: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 14: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 15: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Reviews: