VDOT-U5015 Explosion Proof Smoke Detector 

 

SPECIFICATIONS 

 

OPERATING VOLTAGE

  

12-30 Vdc (24 Vdc nominal)  

 

SMOKE DENSITY

  

1.5% - 2.5% obscuration per foot.  
(4.9% - 8.2% obscuration per meter).  

 

POWER CONSUMPTION

  

3.5 watts maximum (2.75 Watts at 24 Vdc)  
0.674 Watts with no relays energized.  
1.23 Watts with one relay energized.  
2.12 Watts with two relays energized.  
2.68 Watts with three relays energized.  

 

OUTPUT RELAYS

  

Smoke alarm relay, Form C, 5 amperes at 30 Vdc:  
The smoke alarm relay has normally open/ normally closed contacts 
and normally de-energized operation.  

 

Fault relay, Form A, 5 amperes at 30 Vdc:  
The  fault  relay  has  normally  open  contacts  and  normally  energized 
operation.  

 

Auxiliary relay, Form C, 5 amperes at 30 Vdc:  
The auxiliary relay has normally open/normally closed contacts and 
normally de-energized operation.  

 

TEMPERATURE RANGE

  

Operating: 

20°C to +65°C (

4°F to +149°F)  

Storage: 

55°C to +70°C (

67°F to +158°F ).  

 

HUMIDITY RANGE

  

5 to 95% relative humidity. 
 

INGRESS PROTECTION

  

IP44  
Note: Applicable to ceiling mount only  
 

CURRENT OUTPUT

  

 

0-20 mA (±0.3 mA) dc current, with maximum loop resistance of 300 
ohms from 12-17.9 Vdc, 500 ohms from 18 to 19.9 Vdc, and 600 ohms 
from 20-30 Vdc.  
 

TERMINALS

  

UL/CSA rated for 14-18 AWG or 2.5-0.75 mm2 wire.  
 

THREAD OPTIONS

  

3/4 inch NPT or M25.  
Multi-port models available.  
 

ENCLOSURE MATERIAL

  

Polycarbonate / ABS - Smoke Detector.  
Copper-free aluminum (painted) - Junction Box  
 

SHIPPING WEIGHT (Approximate)

  

7.85 lbs (3.56 kg).  
 
 

WARRANTY PERIOD

  

1 year.  

 

DIMENSIONS

  

See Figure 2.  

 

CERTIFICATION

 

For complete approval details, refer to the appropriate Appendix: 

             

         

 

Appendix A - FM        Appendix B - CSA      Appendix C - IECEx  
Appendix D - Additional Approvals

 

 

OPERATION

 

 

 

WARM UP 

 

When the detector is initially powered up, a warm-up period of one 

 two seconds is allotted for internal checks and communication. 

During this time, the LED is off and the current level is 3 mA. After 
the checks are completed, normal operation will be indicated by the 
LED flashing every four seconds (current level is 4 mA).  
 
If the detector is unable to reach the normal operating mode, the 
warm-up period may extend to five seconds, followed by a critical 
fault or an advisory fault (see Table 1 for all current levels). If the 
problem persists, check for any loose wiring connections, ensure 
that the voltage supply is sufficient, and cycle power if necessary.  

 

OUTPUTS 

 

Relays 

 

The U5015 detector is furnished with smoke alarm, fault, and 
auxiliary relays. All three relays are rated to 5 amperes at 30 Vdc.

 

                               

           

 

 
 

Summary of Contents for SmokeWatch VDOT-U5015

Page 1: ...essing plants Petroleum refineries Turbine enclosures Battery rooms HVAC applications The hot swappable sensor module is intrinsically safe and allows live maintenance while under power without de cla...

Page 2: ...om 12 17 9 Vdc 500 ohms from 18 to 19 9 Vdc and 600 ohms from 20 30 Vdc TERMINALS UL CSA rated for 14 18 AWG or 2 5 0 75 mm2 wire THREAD OPTIONS 3 4 inch NPT or M25 Multi port models available ENCLOSU...

Page 3: ...status LATCHING A detector configured for latching operation will remain in an alarm state indefinitely after an alarm occurs NON LATCHING A detector configured for non latching operation will check...

Page 4: ...t be installed in areas in which Ammonia Hydrogen Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each...

Page 5: ...ected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float type battery charging system is recommended If an existin...

Page 6: ...2 to 15 for wiring examples WIRING PROCEDURE Ensure that all cables are terminated properly Conductor insulation should be stripped off with a bare conductor length of 0 2 inch 5 mm minimum and 0 7 in...

Page 7: ...g compartment is the only part of the smoke detector that should be opened by the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke...

Page 8: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 9: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 10: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 11: ...t the Velocity Detection office so that a Return Material Authorization RMA number can be assigned A written statement describing the malfunction must accompany the returned device or component to ass...

Page 12: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 13: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 14: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 15: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Reviews: