VDOT-U5015 Explosion Proof Smoke Detector 

IMPORTANT SAFETY NOTES 

 

CAUTION

 

 

The wiring procedures in this manual are intended to ensure 
proper  functioning  of  the  device  under  normal  conditions. 
However, because of the many variations in wiring codes and 
regulations, total compliance to these ordinances cannot be 
guaranteed. Be certain that all wiring complies with the NEC 
as well as all local codes. If in doubt, consult the authority 
having  jurisdiction  before  wiring  the  system.  Installation 
must be done by a properly trained person.  

 

CAUTION 

 

This  product  has  been  tested  and  approved  for  use  in 
hazardous  areas.  However,  it  must  be  properly  installed  and 
used  only  under  the  conditions  specified  within  this  manual 
and the specific approval certificates. Any device modification, 
improper  installation,  or  use  in  a  faulty  or  incomplete 
configuration will  render warranty and product  certifications 
invalid. 

 
 

CAUTION 

 

The device contains no user serviceable components. Service 
or  repair  should  never  be  attempted  by  the  user.  Device 
repair should be performed only by the manufacturer.  

 

 

CAUTION 

 

The  U5015  is  to  be  installed  in  locations  where  the  risk  of 
mechanical damage is low.  

 

 

LIABILITIES

 

 

The manufacturer’s warranty for this product is void, and all 

liability  for  proper  function  of  the  detector  is  irrevocably 
transferred to the owner or operator in  the event that  the 
device is serviced or repaired by personnel not employed or 
authorized  by  Detector  Electronics  Corporation,  or  if  the 
device  is  used  in  a  manner  not  conforming  to  its  intended 
use. 

 

 

 
 

NOTE 

 

Observe  precautions  for  handling  electrostatic  sensitive 
devices.  

 

 

NOTE 

 

The U5015 should not be installed in areas in which 
Ammonia, Hydrogen Sulfide and Chlorine are normally 
present.

 

 
 

INSTALLATION

 

WARNING

 

 

All entries must contain appropriately rated plugs or fittings. 
It is required that each plug or fitting be wrench-tightened to 
an  appropriate  installation  torque  and  meet  the  minimum 
thread  engagement  requirements  per  the  applicable  local 
standards, codes, and practices in order to retain the defined 
ratings. PTFE sealant  or equivalent  should  be used on NPT 
threads.  

 

NOTE 

 

Detector  housings  must  be  electrically  connected  to  earth 
ground.  Internal  and  external  earth  ground  terminals  are 
provided.  For  AEx  (United  States  Zone)  installations  the 
internal  ground  terminal  shall  be  used  for  the  equipment 
grounding connection. The external terminal can be used for 
supplementary bonding where local codes permit or require. 

 

 
 

NOTE 

 

The U5015 detector uses an internal Intrinsically Safe (I.S.) 
Barrier. Proper NEC I.S. grounding must be ensured 
 

 

 

GREASE/LUBRICATION 

 

To ease installation and future removal, all threaded covers, 
stopping  plugs,  and  thread  adapters  must  be  installed  using 
thread lubricant. The recommended lubricant is a silicone-free 
grease, available from Det-Tronics.  
For  devices  with  NPT  threads,  Teflon  tape  or  thread  seal 
lubricant must be used for enhanced sealing capabilities.  

 

IDENTIFICATION OF DETECTOR MOUNTING 
LOCATIONS 

 

The most effective number and placement of detectors varies 
depending on the conditions on site. The individual designing 
the  installation  must  often  rely  on  experience  and  sound 
judgment  to  determine  the  detector  quantity  and  best 
locations  to  adequately  protect  the  area.  Note  that  it  is 
typically  advantageous  to  locate  detectors  where  they  are 
accessible for maintenance.  
 
For additional information on detector location and spacing, 
visit the National Fire Protection Association's website 
(www.nfpa.org) and refer to the National Fire Alarm and 
Signaling Code, NFPA 72. 
 
 
 
 
 
 
 

Summary of Contents for SmokeWatch VDOT-U5015

Page 1: ...essing plants Petroleum refineries Turbine enclosures Battery rooms HVAC applications The hot swappable sensor module is intrinsically safe and allows live maintenance while under power without de cla...

Page 2: ...om 12 17 9 Vdc 500 ohms from 18 to 19 9 Vdc and 600 ohms from 20 30 Vdc TERMINALS UL CSA rated for 14 18 AWG or 2 5 0 75 mm2 wire THREAD OPTIONS 3 4 inch NPT or M25 Multi port models available ENCLOSU...

Page 3: ...status LATCHING A detector configured for latching operation will remain in an alarm state indefinitely after an alarm occurs NON LATCHING A detector configured for non latching operation will check...

Page 4: ...t be installed in areas in which Ammonia Hydrogen Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each...

Page 5: ...ected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float type battery charging system is recommended If an existin...

Page 6: ...2 to 15 for wiring examples WIRING PROCEDURE Ensure that all cables are terminated properly Conductor insulation should be stripped off with a bare conductor length of 0 2 inch 5 mm minimum and 0 7 in...

Page 7: ...g compartment is the only part of the smoke detector that should be opened by the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke...

Page 8: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 9: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 10: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 11: ...t the Velocity Detection office so that a Return Material Authorization RMA number can be assigned A written statement describing the malfunction must accompany the returned device or component to ass...

Page 12: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 13: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 14: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Page 15: ...www velocitydetection com Doc GLT 311 7 1 Issue 001 Date 28 10 2020 VDOT U5015 Explosion Proof Smoke Detector...

Reviews: