EMR
3
Setup and Operation Manual
Relay Setup Error Codes
57
IB INDICATOR LIGHTS AND IB SELF CHECKS
The tri-color LED, located inside the Interconnection Box, is capable of indicating 4 different states: Green, Red,
Yellow and Off. At start up, the LED flashes the initialization sequence of Off-Green-Red-Yellow-Off indicating that
the IB self-test passed with no errors to display. If one or more Display Heads are communicating with the IB the
LED will flash an Off-Green-Off pattern repeatedly. If one or more IB Relay is active, or a delivery is in process, the
LED will flash an Off-Yellow-Off sequence until all the relays are inactive.
If a communication error occurs, the LED will flash Off-Red-Off indicating a problem. Try swapping the Display
Heads as described above in order to locate the problem. The LED will not indicate a non-functional Display Head.
If a self-test error occurs, the LED will flash an Off-Red-Off-Red-Off sequence indicating a problem. Try swapping
the IB with another IB in order to locate the problem.
If the LED is stuck in one of the 4 states, remove input power from the input terminals for a few seconds. Restore
power and check the LED for the Off-Green-Red-Yellow-Off sequence. If the LED fails to flash in the proper
sequence, replace the IB Circuit Board.
E66 - PRINTER BUSY
The E66 Printer Busy error means that the printer still has information to print from the previous transaction. If a
transaction is complete, but no ticket was put in the printer, the display can be ‘reset’ to zero by pushing the
FINISH button. When the START button is pushed, the Printer Busy Error comes up. The printer icon should be
flashing to indicate there is information to be printed. The ability to ‘reset’ the register is based on a ticket sensing
switch inside the printer that clears once a ticket has been removed. The data that needs to be printed is still
however, in the printer’s buffer memory as indicated by the flashing icon.
Another possibility is that the previous transaction printed some or most of the information on the ticket, but the
ticket was not long enough to print all the information (the printer icon should be flashing). Install a blank ticket into
the printer and the remaining information will finish printing. Keep in mind that if the operator thinks all of the lines
printed, there may still be blank lines in the format that have to print to complete the ticket.
Cycling the printer power will clear the printer memory and the Printer Busy Error. However, the transaction record
is in the EMR
3
system memory and can be recalled using view records or printing records.
Hardware and Printer Busy
If one of the communications wires between the printer and the IB is not connected, the printer will not print, but
the printer icon will flash after a transaction. When the ticket is removed, the register can be reset by pushing
FINISH, but again, when the START button is pushed, the Printer Busy Error will show because there is still
information from the previous transaction to print. Cycling the power will clear the error as described above,
allowing the next transaction to start.
EXC ERROR ####
These are 4-digit coded exception processing errors associated with booting up the EMR³ system. Try cycling
power Off and On before replacing the Display Head.
Relay Setup Error Codes
Relay setup errors occur while entering relay or preset information in Setup Mode. When using 2-stage valves,
relay 1 is used to control the fast-flow solenoid and relay 2 is used to control the single flow solenoid. Under the
RELAY CONTROL settings, two values are used to knockoff each solenoid prior to the end of a preset delivery:
SET SLOW FLOW (relay 1) and SET ADVANCE STOP (relay 2).