IQ Control Box Installation and Owner’s Manual
Determine the Motor Type
12
Table 3 lists UMP weights and lengths and Table 4 lists pump shut off pressures.
The weights and lengths listed below are approximate values and will vary due to
manufacturing tolerances.
The optional trapper intake screen is available as a field installed accessory. Trapper options will increase the
length of the UMP by 3.3 inches (83 mm). For installation instructions, see Red Jacket installation instructions
#051-256-1. For models with floating suction adapter, add 2-3/8 inches (59 mm) and 4 pounds (1.8 kg).
Table 3. UMP Model Dimensions
Franklin Motor
(Use these lengths for UMPs
with end view A shown in
Faradyne Motor
(Use these lengths for UMPs
with end view B shown in
Weight
UMP Model
HP
in.
mm
in.
mm
lb.
kg
UMP33U1, AGP33R1
1/3
15-1/2
390
15-3/8
391
24
11.0
UMP75U1,
E85
AGUMP75S1
3/4
17-3/4
447
17-5/8
448
28
12.7
UMP75U3-3, AGUMP75S3-3
3/4
20
507
19-7/8
505
30.5
13.9
UMP150U1,
E85
AGUMP150S1
1-1/2
20-1/2
519
20-5/8
524
34
15.5
X3P150U1,
E85
X3AGUMP150S1
1-1/2
21-1/4
540
21-1/2
546
35
15.8
UMP150U3-3, AGUMP150S3-3
1-1/2
22-1/4
565
22-1/4
565
34
15.5
X4P150U3, X4GUMP150S3
1-1/2
22-3/4
576
22-7/8
581
35
15.9
UMP200U1-3,
E85
AGUMP200S1-3
2
24-1/4
618
24-5/8
626
36
16.3
UMP200U3-4, AGUMP200S3-4
2
26
660
26-1/4
667
38
17.2
Table 4. Approximate Pump Shut Off Pressures
UMP Model
Approximate Shut Off Pressure
AGUMP33S1, UMP33R1
25 psi (172 kPa) .74 SG @ 60°F (15°C)
E85
AGUMP75S1, UMP75U1
28 psi (193 kPa) .74 SG @ 60°F (15°C)
E85
AGUMP150S1, UMP150U1
30 psi (207 kPa) .74 SG @ 60°F (15°C)
E85
X3AGUMP150S1, X3UMP150U1
43 psi (297 kPa) .74 SG @ 60°F (15°C)
AGUMP75S3-3, UMP75U3-3
30 psi (207 kPa) .74 SG @ 60°F (15°C)
AGUMP150S3-3, UMP150U3-3
32 psi (220 kPa) .74 SG @ 60°F (15°C)
X4AGUMP150S3, X4UMP150U3
40 psi (275 kPa) .74 SG @ 60°F (15°C)
E85
AGUMP200S1-3, UMP200U1-3
43 psi (297 kPa) .74 SG @ 60°F (15°C)
AGUMP200S3-4, UMP200U3-4
43 psi (297 kPa) .74 SG @ 60°F (15°C)