background image

 

 

Humidistat TCY-BH-U

 

 

Doc:70-07-0102, V1.1, Date: 20100504 

© Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

Connection terminals  

 
Terminal-description:  

1.

 

Connection for power-supply (24 V AC/DC, ±10%). In case of DC, 

connect the negative power-terminal. Common connection for analog in- and 
outputs.  

2.

 

Connection for power-supply (24 V AC/DC, ±10%). In case of DC, 

connect the positive power-terminal 

3.

 

Switched contact “DO 1” Humidify or Fan (Max. 2 (1.2A) 

4.

 

Switched contact “DO 1” Humidify or Fan (Max. 2 (1.2A) 

5.

 

Switched contact “DO 2” Dehumidify or Fan (Max. 2 (1.2A) 

6.

 

Switched contact “DO 2” Dehumidify or Fan (Max. 2 (1.2A) 

7.

 

Thermistor input “RT” (Thermistor Sxx-Tn10) 

8.

 

Thermistor input “RT” (Thermistor Sxx-Tn10) 

 
 
 
 

 

Mechanical Design and installation 

The unit consists of two parts: (a) The power case with attached mounting plate and (b) the front part.  

Mounting location 

 

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature. 

 

Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical 
equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front retaining screw is at 
the bottom. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) from the surface of the 
mounting plate.  

3.

 

Ensure that the jumpers are set correctly.  

4.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.  

5.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle way 
until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is normal. 
Do not use excessive force!  

6.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to the 
mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the screw too 
much. 

TCY-BH-U 

DO1

 

DO2

 

DO2

 

RT 

RT 

DO1

 

24

V

 

0

V

 

Summary of Contents for TCY-BH-U

Page 1: ...ation humidifiers and dehumidifiers without fan support General Description The TCY BH U is a stand alone electronic binary humidity stat The TCY BH U features one internal humidity sensor one externa...

Page 2: ...NTC Sxx Tn10 sensor 40 70 C 40 158 F Accuracy 40 0 C 40 32 F 0 5 K 0 50 C 32 122 F 0 2 K 50 70 C 122 158 F 0 5 K Signal Outputs Digital Switching Outputs Switching type Switching power DO1 DO2 Relays...

Page 3: ...0 30 VDC RT Temperature input for setback NTC 10k 25 C 77 F CP10 1 YB1 Binary output 1 Humidify 0 24 VAC or 0 30 VDC YB2 Binary output 2 if CP11 ON Fan 0 24 VAC or 0 30 VDC RT Temperature input for se...

Page 4: ...uipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 C...

Page 5: ...meters and set points are memorized and don t need to be reentered Depending on UP 05 the unit will remain switched off switch on automatically or return to the operation mode it was in before the pow...

Page 6: ...mode is used for rooms such as lecture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is activ...

Page 7: ...in the large digits and CALH or CAL t in the small Pressing OPTION will reveal the current calibration value of the humidity sensor CALH or the temperature input CAL t Change the value with the UP DO...

Page 8: ...pressing the OPTION button Three triangles will show up on the lower right and indicate that the parameter may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPT...

Page 9: ...ll increase the number of switching cycles and thus the wear on associated equipment Delay OFF Prevents a too short running cycle for the control output by setting a minimum running time Delay ON Prev...

Page 10: ...and the humidistat will first activate the fan wait the required start delay time CP12 and then activate the control output This will ensure stable air for humidification or de humidification The cont...

Page 11: ...0 10 CP 05 Dead zone between humidifying de humidifying set point XDZ 0 100 10 CP 06 Delay on humidify de humidify change over 0 255 min 5 min CP 07 Switching Hysteresis 0 100 3 CP 08 Delay OFF Minimu...

Reviews: