Humidistat TCY-BH-U

 

 

Doc:70-07-0102, V1.1, Date: 20100504 

© Vector Controls GmbH, Switzerland 

Page 6 

Subject to alteration 

Clock Operation and Time Schedules (Deluxe Version) 

TCY-BH-U-D contains a real time clock. Up to 16 mode changes (not defined, Off, Economy, Comfort, University mode) based 
on weekdays and time may be programmed. See chapter operation on how to program switch times.  
The different scheduled mode changes have these effects: 

Name on display 

Function 

Override reset 

no 

Switching event not used 

 

OFF 

Operation mode changes to off mode 

Reset is active 

ECO 

Operation mode changes to economy mode 

Reset is not active 

ON 

Operation mode changes to comfort mode 

Reset is not active 

UNI 

Operation mode does not change  

Reset is not active 

 
UNI: University mode: This switching mode is used for rooms such as lecture rooms and auditoriums that might be occupied 
during a certain time. During this time the reset is not active. The unit will not start itself when UNI mode is active. It still 
needs to be manually activated. This is to avoid unnecessary heating or cooling of such rooms while they are not occupied.  
Override reset function: The override reset applies when the unit is manually switched on, while in scheduled off mode. The 
unit will switch automatically off when the reset time defined in UP-13 expires. Setting UP-13 to 0 disables the override reset.  
A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined. See chapter 
operation, advanced settings for instructions on how to set the time. 

Error messages 

The TCY-BH-U may display the following error condition:  

Err1:

 

Humidity sensor faulty. The humidity sensor is damaged.  

Err2:

 

External input for temperature setback missing or damaged.  

Summary of Contents for TCY-BH-U

Page 1: ...ation humidifiers and dehumidifiers without fan support General Description The TCY BH U is a stand alone electronic binary humidity stat The TCY BH U features one internal humidity sensor one externa...

Page 2: ...NTC Sxx Tn10 sensor 40 70 C 40 158 F Accuracy 40 0 C 40 32 F 0 5 K 0 50 C 32 122 F 0 2 K 50 70 C 122 158 F 0 5 K Signal Outputs Digital Switching Outputs Switching type Switching power DO1 DO2 Relays...

Page 3: ...0 30 VDC RT Temperature input for setback NTC 10k 25 C 77 F CP10 1 YB1 Binary output 1 Humidify 0 24 VAC or 0 30 VDC YB2 Binary output 2 if CP11 ON Fan 0 24 VAC or 0 30 VDC RT Temperature input for se...

Page 4: ...uipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 C...

Page 5: ...meters and set points are memorized and don t need to be reentered Depending on UP 05 the unit will remain switched off switch on automatically or return to the operation mode it was in before the pow...

Page 6: ...mode is used for rooms such as lecture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is activ...

Page 7: ...in the large digits and CALH or CAL t in the small Pressing OPTION will reveal the current calibration value of the humidity sensor CALH or the temperature input CAL t Change the value with the UP DO...

Page 8: ...pressing the OPTION button Three triangles will show up on the lower right and indicate that the parameter may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPT...

Page 9: ...ll increase the number of switching cycles and thus the wear on associated equipment Delay OFF Prevents a too short running cycle for the control output by setting a minimum running time Delay ON Prev...

Page 10: ...and the humidistat will first activate the fan wait the required start delay time CP12 and then activate the control output This will ensure stable air for humidification or de humidification The cont...

Page 11: ...0 10 CP 05 Dead zone between humidifying de humidifying set point XDZ 0 100 10 CP 06 Delay on humidify de humidify change over 0 255 min 5 min CP 07 Switching Hysteresis 0 100 3 CP 08 Delay OFF Minimu...

Reviews: