background image

 

 

Humidistat TCY-BH-U

 

 

Doc:70-07-0102, V1.1, Date: 20100504 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Control Functions 

The controller is designed to control binary heating and/or cooling systems.  

Setpoint 

Minimum and Maximum Set Point Limits

: Limits the adjustable range of the loop set point. The limits for heating and 

cooling sequence may be chosen individually.  

Control Sequence 

Economy set point shift X

SBY

: This function shifts the set point while the operation mode is Economy. The heating set 

point W

H

 is reduced and the cooling set point W

C

 increased by the value of the Economy set point shift X

SBY

.  

Dead Zone Span X

DZ

: The dead zone span lies between the humidifying and the de-humidifying set point.  

Switching Hysteresis

: Defines the difference between switching on and switching off an output. A small hysteresis will 

increase the number of switching cycles and thus the wear on associated equipment.  

Delay OFF:

 Prevents a too short running cycle for the control output by setting a minimum running time.  

Delay ON:

 Prevents a too short stopping cycle for the control output by setting a minimum stopping time. 

Binary Control  

 

Room 

Humidity 

  w

HU

 

Setpoint Humidifying Mode 

D

Z

 Dead 

Zone  

w

DH 

Setpoint De-humidifying Mode  X

SBY

 

Economy 

Shift 

  X

H

 Hysteresis 

Q

HU

 Humidifying 

Output  

Q

DH

 De-humidifying 

Output 

Temperature setback (TSET) 

Shift the humidity set point towards a defined TSET setpoint 

CP 15

 depending on the outdoor temperature.  

Temperature setback becomes active when the outside temperature drops below the activation limit of temperature setback 

CP17

. The full temperature setback is reached when the temperature reaches the full limit 

CP16

. The actual set point will in 

this case be equal to the TSET setpoint.  
Temperature setback may be enabled with 

CP14

 

Temperature Setback 

 

T [°C, F] 

CP16 

CP17 

CP15

Setpoint 

W

ON

OFF

T [°C, F] 
 

 

X

SBY

 

W

X

SBY

 

X

DZ

 

W

X

H

 

Q

DH

 

 

Q

HU

 

Summary of Contents for TCY-BH-U

Page 1: ...ation humidifiers and dehumidifiers without fan support General Description The TCY BH U is a stand alone electronic binary humidity stat The TCY BH U features one internal humidity sensor one externa...

Page 2: ...NTC Sxx Tn10 sensor 40 70 C 40 158 F Accuracy 40 0 C 40 32 F 0 5 K 0 50 C 32 122 F 0 2 K 50 70 C 122 158 F 0 5 K Signal Outputs Digital Switching Outputs Switching type Switching power DO1 DO2 Relays...

Page 3: ...0 30 VDC RT Temperature input for setback NTC 10k 25 C 77 F CP10 1 YB1 Binary output 1 Humidify 0 24 VAC or 0 30 VDC YB2 Binary output 2 if CP11 ON Fan 0 24 VAC or 0 30 VDC RT Temperature input for se...

Page 4: ...uipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 C...

Page 5: ...meters and set points are memorized and don t need to be reentered Depending on UP 05 the unit will remain switched off switch on automatically or return to the operation mode it was in before the pow...

Page 6: ...mode is used for rooms such as lecture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is activ...

Page 7: ...in the large digits and CALH or CAL t in the small Pressing OPTION will reveal the current calibration value of the humidity sensor CALH or the temperature input CAL t Change the value with the UP DO...

Page 8: ...pressing the OPTION button Three triangles will show up on the lower right and indicate that the parameter may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPT...

Page 9: ...ll increase the number of switching cycles and thus the wear on associated equipment Delay OFF Prevents a too short running cycle for the control output by setting a minimum running time Delay ON Prev...

Page 10: ...and the humidistat will first activate the fan wait the required start delay time CP12 and then activate the control output This will ensure stable air for humidification or de humidification The cont...

Page 11: ...0 10 CP 05 Dead zone between humidifying de humidifying set point XDZ 0 100 10 CP 06 Delay on humidify de humidify change over 0 255 min 5 min CP 07 Switching Hysteresis 0 100 3 CP 08 Delay OFF Minimu...

Reviews: