Humidistat TCY-BH-U

 

 

Doc:70-07-0102, V1.1, Date: 20100504 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alteration 

Selection of devices and sensors 

External temperature sensors: Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-
Tn10-15 as Duct sensor and SOA-Tn10 as outdoor sensor.  
Binary auxiliary devices: E.g. humidifiers, de-humidifiers and fans.  Do not directly connect devices that exceed 2(1.2)A. 
Observe startup current on inductive loads!  
 

Technical Specification 

Power Supply 

Operating Voltage 

24 V AC/DC ± 10 %, 50…60 Hz 

 

Power Consumption 

Max. 2 VA 

 

Electrical Connection 

Terminal Connectors,  
wire 0.34…2.5 mm

2

 (AWG 24…12)

 

 Deluxe 

type 

only: 

Power backup for real time clock 

 
Min 48h if charged for 24h 

Signal Inputs 

Humidity Input:  
Range 
Accuracy 
 

Hysteresis 

Element: Polymer-Based Capacity Sensor 
0…100 % r.H.  
10%...90% r.H. 

±

 5.0 % 

0…10% and 90…100% 

±

 7.0 % 

±1% r.H. 

 Temperature 

Input 

Range 

External NTC (Sxx-Tn10 sensor):  
-40…70 °C (-40…158 °F) 

 

Accuracy 

-40…0 °C (-40…32 °F): 0.5 K 
0…50 °C (32…122 °F): 0.2 K 
50…70 °C (122…158 °F): 0.5 K 

Signal Outputs 

Digital Switching Outputs 

Switching type 

Switching power 

DO1…DO2 
Relays, Normally open 

2(1.2) A 

Environment Operation 

Climatic Conditions 
Temperature 

Humidity 

To IEC 721-3-3 
class 3 K5 
0°C …50°C (32°F…122°F) 

<95% R.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 

Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25°C…70°C (-13°F…158°F) 
<95% R.H. non-condensing 

class 2M2 

Standards 

 

conform according to  
EMC Standard 89/336/EEC 
EMEI Standard 73/23/EEC 

 
EN 61 000-6-1/ EN 61 000-6-3 

 

Product standards 

Automatic electrical controls for 
household and similar use 
Special requirement on humidity 
dependent controls 

 
EN 60 730 –1 
 
EN 60 730 – 2 - 9 

 

Degree of Protection 

IP30 to EN 60 529 

 

Safety Class 

III (IEC 60536) 

Housing 

Cover, back part 
Mounting Plate 

Fire proof ABS plastic (UL94 class V-0) 
Galvanized Steel 

General 

Dimensions (H x W x D)  

Front part:  

Power case: 

 
112 x 73 x 15 mm (4.4” x 2.9” x 0.6”)  

ø 58 x 32 mm (ø 2.3” x 1.3”) 

 

Weight (including package) 

270g 

 

Summary of Contents for TCY-BH-U

Page 1: ...ation humidifiers and dehumidifiers without fan support General Description The TCY BH U is a stand alone electronic binary humidity stat The TCY BH U features one internal humidity sensor one externa...

Page 2: ...NTC Sxx Tn10 sensor 40 70 C 40 158 F Accuracy 40 0 C 40 32 F 0 5 K 0 50 C 32 122 F 0 2 K 50 70 C 122 158 F 0 5 K Signal Outputs Digital Switching Outputs Switching type Switching power DO1 DO2 Relays...

Page 3: ...0 30 VDC RT Temperature input for setback NTC 10k 25 C 77 F CP10 1 YB1 Binary output 1 Humidify 0 24 VAC or 0 30 VDC YB2 Binary output 2 if CP11 ON Fan 0 24 VAC or 0 30 VDC RT Temperature input for se...

Page 4: ...uipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 C...

Page 5: ...meters and set points are memorized and don t need to be reentered Depending on UP 05 the unit will remain switched off switch on automatically or return to the operation mode it was in before the pow...

Page 6: ...mode is used for rooms such as lecture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is activ...

Page 7: ...in the large digits and CALH or CAL t in the small Pressing OPTION will reveal the current calibration value of the humidity sensor CALH or the temperature input CAL t Change the value with the UP DO...

Page 8: ...pressing the OPTION button Three triangles will show up on the lower right and indicate that the parameter may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPT...

Page 9: ...ll increase the number of switching cycles and thus the wear on associated equipment Delay OFF Prevents a too short running cycle for the control output by setting a minimum running time Delay ON Prev...

Page 10: ...and the humidistat will first activate the fan wait the required start delay time CP12 and then activate the control output This will ensure stable air for humidification or de humidification The cont...

Page 11: ...0 10 CP 05 Dead zone between humidifying de humidifying set point XDZ 0 100 10 CP 06 Delay on humidify de humidify change over 0 255 min 5 min CP 07 Switching Hysteresis 0 100 3 CP 08 Delay OFF Minimu...