Humidistat TCY-BH-U

 

 

Doc:70-07-0102, V1.1, Date: 20100504 

© Vector Controls GmbH, Switzerland 

Page 5 

Subject to alteration 

Display and Operation 

The operation terminal uses an LCD display and four operation buttons.  

 

Legend: 

1.

 

4-digit display of current value, time,  
control parameter or set point. 

2.

 

Unit of displayed value, °C, °F, % or none 

3.

 

Indication of active binary stage,  
running down to up = humidifying 
running up to down = de-humidifying 

4.

 

4-digit display of current value, time, control 
parameter or set point. 

5.

 

Operation modes: 

Comfort mode, 

 Economy mode, 

OFF

 Energy Hold Off  

6.

 

Symbols:  

Setback Active 

Schedule Set 

Fan Active 

TSET Error 

 

 

 

T

 

7.

 

Buttons for operating the controller 

POWER button: Pressing the button less than 2 sec toggles Economy and comfort modes. Pressing the 
button for more than 2 seconds switches the unit off.  
UP and DOWN buttons: change setpoints and parameters

  

OPTION button: display temperature if temperature setback is enabled and access advanced setup.  

 

Power Failure 

All the parameters and set points are memorized and don’t need to be reentered. Depending on UP-05 the unit will remain 
switched off, switch on automatically or return to the operation mode it was in before the power failure. The deluxe version 
includes a real time clock with a 48h backup battery powered through a super capacitor. The time does not need to be re-
entered after a power failure.  

Operation Modes 

 

Comfort: The unit is in full operation mode. All the control functions are operating according to their setpoints. The 

unit displays occupied mode.  

 

Economy: The set point is shifted according to parameters FC-04. The heating parameter is shifted down and cooling 

parameter up. The unit displays unoccupied mode Economy operation may be disabled with UP-06.  

 

Off mode: The unit is switched off. All outputs are off. Off and current time is displayed.  

Activation of operation modes 

 

Via operation terminal 

 

Clock: (Deluxe version only) Operation modes may automatically be switched according to time of day and weekday. 
The clock symbol will be displayed if time programs are activated.  

Note: Time programs will not operate if operation mode is set to OFF by remote control, or if time is not set.  

2

 

3

 

4

 

7

 

1

 

6

 

5

 

Summary of Contents for TCY-BH-U

Page 1: ...ation humidifiers and dehumidifiers without fan support General Description The TCY BH U is a stand alone electronic binary humidity stat The TCY BH U features one internal humidity sensor one externa...

Page 2: ...NTC Sxx Tn10 sensor 40 70 C 40 158 F Accuracy 40 0 C 40 32 F 0 5 K 0 50 C 32 122 F 0 2 K 50 70 C 122 158 F 0 5 K Signal Outputs Digital Switching Outputs Switching type Switching power DO1 DO2 Relays...

Page 3: ...0 30 VDC RT Temperature input for setback NTC 10k 25 C 77 F CP10 1 YB1 Binary output 1 Humidify 0 24 VAC or 0 30 VDC YB2 Binary output 2 if CP11 ON Fan 0 24 VAC or 0 30 VDC RT Temperature input for se...

Page 4: ...uipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 C...

Page 5: ...meters and set points are memorized and don t need to be reentered Depending on UP 05 the unit will remain switched off switch on automatically or return to the operation mode it was in before the pow...

Page 6: ...mode is used for rooms such as lecture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is activ...

Page 7: ...in the large digits and CALH or CAL t in the small Pressing OPTION will reveal the current calibration value of the humidity sensor CALH or the temperature input CAL t Change the value with the UP DO...

Page 8: ...pressing the OPTION button Three triangles will show up on the lower right and indicate that the parameter may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPT...

Page 9: ...ll increase the number of switching cycles and thus the wear on associated equipment Delay OFF Prevents a too short running cycle for the control output by setting a minimum running time Delay ON Prev...

Page 10: ...and the humidistat will first activate the fan wait the required start delay time CP12 and then activate the control output This will ensure stable air for humidification or de humidification The cont...

Page 11: ...0 10 CP 05 Dead zone between humidifying de humidifying set point XDZ 0 100 10 CP 06 Delay on humidify de humidify change over 0 255 min 5 min CP 07 Switching Hysteresis 0 100 3 CP 08 Delay OFF Minimu...