background image

 

TLC3-BCR-U Thermostat 

C

ONTROL 

C

ONFIGURATION

 

 

Doc: 70-00-0294, V3.1, Date: 20140508 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Output configuration 

Parameter  Description 

Range 

Default 

CP 13 

Output setting, Binary, PWM or 3-point: 
0 = Binary or PWM (See CP14 for assignment of Y1 and Y2) 

1 = 3-point binary output (Y1 open, Y2 close) 

2 = 3-point floating output (Y1 open, Y2 close) 

0…2 

Binary / PWM 

CP 14 

Reversing valve in binary mode  

0 = no reversing valve, one stage only (Y1 Heating, Y2 Cooling) 

1 = rev. valve while heating  (Y1 stage 1, Y2 rev valve) 

2 = rev. valve while cooling  (Y1 stage 1, Y2 rev valve) 

3 = no reversing valve, two stages (Y1 stage 1, Y2 stage 2) 

0...3 

CP 15 

Running Time in 3-point mode 

0…255 s 

90 s 

CP 16 

PWM cycle time, 0 disables PWM mode 

0…100 min 

 

On-Off control 

Two devices may be controlled in case the output setting is 0 (CP13). Y1 controls a heating and Y2 a cooling 

device if in single stage mode. If in 2-stage mode (CP14 = 3) Y1 controls stage 1 and Y2 stage 2. The switching 
span for stage 2 is defined by the P-band (X

PH

, X

PC 

).

 

 

PWM output: 

 

Fine tuned proportional control with one binary output is possible thanks to Pulse Width Modulation (PWM). 

Conventional fan coil controllers will operate in an on-off control mode. The valve is opened until the setpoint is 

reached and then closed. As heating or cooling systems are normally slow acting (heating slower than cooling), 

this will lead to a relatively wide fluctuation of the room temperature as the temperature will overshoot the 

setpoint and undershoot the hysteresis.  

With PWM the ON-OFF ratio of the output is determined by the proportional controller. The interval is the PWM 

cycle time. We recommend 8 min for cooling systems and 15min for heating systems. Cycle times depend on the 

room and the heating or cooling device.  

Set the cycle time to 0 to disable PWM and activate conventional on-off control mode (Factory default). 

 

3-point output 

A 3 point actuator has an open and a close input. Applying power to the open input will drive the valve or damper 

open, applying power to the close input will drive the valve or damper to the closed position. 

 

The running time of the actuator may be preset. We recommend to enter the maximum running time under 

maximum load in order to make sure that the valve can fully close and fully open in any circumstance.  

In order to open the valve or damper Y1 will be activated for the preset amount of time. After the expiration of 

the running time Y1 and Y2 will be OFF. The valve is closed by activating Y2 for the preset amount of time.  

 

3-point on-off mode 

In on-off mode the actuator is either fully opened or fully closed. This is used for some (mostly fast running) zone 

valves that are not equipped for frequent start – stop cycles. Binary control is active in this mode.  

 

3-point floating mode 

The actuator position is modulated by the controller using proportional control. The position is calculated based on 

summarized opening and closing times. The software contains a synchronization algorithm to guarantee accurate 

positioning even after extended running time. Proportional control is active. 

 

Reversing valve 

In binary output mode a reversing valve option is available. A reversing valve is used where a compressor is used 

to generate heating and cooling. Select 1 if the reversing valve is to be activated while in heating mode, select 2 if 
the reversing valve is active while the unit is in cooling mode.

 

The reversing valve will open based on its settings once the operation mode is ON and the either the heating or 

the cooling sequence is active.  

 

Control Logic if CP13 = 0  

The proportional control function calculates the output based on the difference between setpoint and measured 

value. The proportional band (P-band) defines the difference between setpoint and measured value which will 

result in a 100% output. For example, with a heating or reverse 0-10v control sequence, and a 2.0°C (4.0°F) P-

band value, at 10v the controller will be 2.0°C (4.0°F) below setpoint. This is the working range of the 

proportional control sequence. 

 

System type 

CP14 

Y1 

Y2 

2 pipe system heat or cool 

Heat 

Cool 

4 pipe system Heating mode 

Heat 

 

4-pipe system Cooling mode 

 

Cool 

4-pipe reversing valve on Heat 

Stage 1 

Rev valve (in heat mode) 

4-pipe reversing valve on Cool 

Stage 1 

Rev valve (in cool mode) 

2-pipe system heat of cool, 2 stages 

Stage 1 

Stage 2 

 

 

Summary of Contents for 40-10 0160

Page 1: ...n General temperature control General TLC3 BCR U 1 independent temperature control loop with 1 heating and 1 cooling sequence 1 internal temperature sensor 1 external temperature input 1 auxiliary inp...

Page 2: ...ng Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards...

Page 3: ...e wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is...

Page 4: ...ints are memorized and do not need to be re entered Upon return of power Set Parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retai...

Page 5: ...to Pro 4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set...

Page 6: ...f inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to...

Page 7: ...rnal temperature sensor 10 to 10 in 0 1 steps Sensor is factory calibrated use this feature for field adjustment only as required 10 10 0 UP 09 Enable Frost Protection Switches to heating mode and act...

Page 8: ...t persist for the length of time set with this parameter before the controller switches Prevents activation of a sequence during a short term change in temperature in order to protect equipment with c...

Page 9: ...alve or damper to the closed position The running time of the actuator may be preset We recommend to enter the maximum running time under maximum load in order to make sure that the valve can fully cl...

Page 10: ...ting X2 input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP17 3 Heat Cool changeover Switch heating and cooling...

Reviews: