Display and Operation 

 

Operation mode 

 

Comfort (occupied) 

All control functions operating per set points. 

 

Economy (unoccupied): 

Set points shifted according to 

Parameters CP04.

 

Economy mode and setpoint shift may be disabled with UP06 

OFF 

Energy Hold Off 

Outputs are off, inputs monitored for alarm condition 

 

Heating 

Output activates if temperature lower than setpoint 

 

Cooling 

Output activates if temperature higher than setpoint 

 

Manual mode 

Deluxe only: Override of time schedule active.  

 

Schedule 

Deluxe only: Time schedule is active 

 

Standard display (Parameters UP10, UP11) 

 

Active when no key has been pressed for 30 seconds. 

 

Contents may be chosen with parameters.  

Loop display 

 

Active when changing set points. Large digits show input value. Small digits show set point. Vertical bars show 

analog output value. Arrows in position 1, 2 and/or 3 show active binary (digital) output stages 

Power Failure 

 

All parameters and set points are memorized and do not need to be re-entered.  

 

Upon return of power: Set 

Parameter UP05

 to keep the unit off, switch on, or operation mode before power failure.  

 

Clock and time schedule settings retained for 48 hours (after powered for at least 10 hours). 

Error messages 

Err1:

 

Error temperature sensor. The internal temperature sensor may be damaged or not present  

FP:

 

Steady: Frost protection is active.  

Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key. 

 

 

Left (POWER):  

Press < 2 sec.: Toggle Economy - 
Comfort mode or switch from OFF to ON 
Press > 2 sec.: Turn unit OFF. Text OFF 
displayed with current time (deluxe) 
temperature (standard) 
(Parameter setting: Return to previous 
level. ESC) 

Up :  

Increase setpoint  
(Parameter setting: scroll 
menu options and parameters) 

Down: 

Decrease setpoint  

(Parameter setting: scroll menu options 
and parameters) 

 

Mode 

Display of operation mode 

 
 

Large Digits: 

Display of input or 

parameter value. 

Vertical Bar: 

(Active stage or 

proportional output in 10% steps) 
 

Small Digits:  

Display of setpoint, clock or 
parameter number. 
 

Right (OPTION)  

Press < 2 sec.: Select setpoint 
Press > 2 sec.: Manual H/C change 
(Parameter setting: ENTER to select 
menu option, accept parameter change) 

Indicators 

1 Remote temperature sensor 

Summary of Contents for 40-10 0160

Page 1: ...n General temperature control General TLC3 BCR U 1 independent temperature control loop with 1 heating and 1 cooling sequence 1 internal temperature sensor 1 external temperature input 1 auxiliary inp...

Page 2: ...ng Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards...

Page 3: ...e wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is...

Page 4: ...ints are memorized and do not need to be re entered Upon return of power Set Parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retai...

Page 5: ...to Pro 4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set...

Page 6: ...f inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to...

Page 7: ...rnal temperature sensor 10 to 10 in 0 1 steps Sensor is factory calibrated use this feature for field adjustment only as required 10 10 0 UP 09 Enable Frost Protection Switches to heating mode and act...

Page 8: ...t persist for the length of time set with this parameter before the controller switches Prevents activation of a sequence during a short term change in temperature in order to protect equipment with c...

Page 9: ...alve or damper to the closed position The running time of the actuator may be preset We recommend to enter the maximum running time under maximum load in order to make sure that the valve can fully cl...

Page 10: ...ting X2 input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP17 3 Heat Cool changeover Switch heating and cooling...

Reviews: