background image

WHITE-RODGERS 90 SERIES

1F95CA-391

MULTI-STAGE/HEAT PUMP INSTALLATION/CONFIGURATION

This White-Rodgers Digital Thermostat uses
microcomputer technology to provide precise
time, humidity, and temperature control. This
thermostat offers the flexibility to design

1F95CA-391: 7 Day programming;

residential applications.

ELECTRICAL  DATA

Electrical Rating:

20 to 30 VAC, 50/60 Hz with common
0.05 to 1.5 Amps per terminal
2.5 Amps maximum total load (all
terminals combined).
Hardwired only.
C terminal is required.

INSTALLATION

Part No. 37-6583A

0504

DESCRIPTION

SPECIFICATIONS

heating and cooling programs that fit
building needs. This thermostat is adaptable
to most 24 volt residential forced air multi-

Standard Systems:

Multi-stage gas, oil, electric.

Single-stage or two-stage compressor

heat pump.

THERMAL DATA

Setpoint Temperature Range:

45° to 99°F (7° to 37°C)

Operating Ambient Temperature:

32° to 110°F (0° to 43°C)

Operating Humidity Range:

90% non-condensing max.

Shipping Temperature Range:

-4° to 149°F (-20° to 65°C)

PRECAUTIONS

Do not short out terminals on gas valve
or primary control to test. Short or
incorrect wiring will damage thermostat
and could cause personal injury and/or
property damage.

Do not use on circuits exceeding
specified voltage. Higher voltage will
damage thermostat and could cause
shock or fire hazard.

Thermostat installation and all compo-
nents of the system shall conform to
Class II circuits per the NEC code.

To prevent electrical shock and/or
equipment damage, disconnect electric
power to system at main fuse or circuit
breaker box until installation is
complete.

Read all instructions thoroughly before
beginning installation.

This thermostat is intended for use with a
low voltage system. Do not use on a line
voltage system.

CAUTION

!

WARNING

!

Do not exceed ratings shown in the Specifi-
cations section, above. If in doubt about the
electrical ratings of your heating/cooling
system, have it inspected by a qualified
heating and air conditioning contractor or
licensed electrician.

All wiring must conform to local and
national electrical codes and ordinances.

This control is a precision instrument, and
should be handled carefully. Rough handling
or distorting components could cause the
control to malfunction.

NOTE

stage or heat pump systems with electric or
fossil fuel auxiliary.

White-Rodgers is a division 

of Emerson Electric Co.

www.white-rodgers.com

Summary of Contents for 1F95CA-391

Page 1: ...t or incorrect wiring will damage thermostat and could cause personal injury and or property damage Do not use on circuits exceeding specified voltage Higher voltage will damage thermostat and could cause shock or fire hazard Thermostat installation and all compo nents of the system shall conform to Class II circuits per the NEC code To prevent electrical shock and or equipment damage disconnect e...

Page 2: ...es from the old thermostat one at a time DO NOT let the wires fall back into the wall Install the new thermostat using the follow ing procedures ATTACH BASE TO WALL Remove packing material from the thermo stat Place fingers of one hand on the center top and bottom portion of the thermostat Grasp the base in the other hand on top and bottom center and gently pull straight out Forcing or prying on t...

Page 3: ...ection for proper thermostat configuration THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor Comfort Alert Interface Module THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor Comfort Alert Interface Module 3 THERMOSTAT TERMINALS Lower SYSTEM C R HM W2 DHM E W1 Y2...

Page 4: ...YSTEM ONLY If you have a single stage compressor system see the diagram below A relay customer provided should be installed as shown in Fig 5 to switch the fan speed to the next lower speed on a call for dehumidification from the thermostat The reduction in air flow allows the coil to remove more humidity from the air The relay should be rated for blower motor load Since this configuration reduces...

Page 5: ...h 6 step 6 is for heat pump only These items allow the cycle times in heating cooling and auxiliary heat pump systems only to be increased or decreased The factory set values can be adjusted higher for longer cycles or lower for shorter cycles NOTE Some manufacturers still instruct you to set the anticipator to the current draw of the equipment That instruction applies only to mercury bulb or mech...

Page 6: ... in sequence after HEAT if HEAT PUMP is selected Program RUN TIME FWD Heat Pump ONLY TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD 6 SET CYCL AUX 08 1 to 40 9 HEAT FAN DELA OFF 00 0 to 127 seconds 10 PUMP ON OFF 11 COMP OFF DELA 60 0 to 99 7 COOL FAN DELA OFF 00 0 to 127 seconds 8 5 5 5 5 5 5 5 5 7 7 7 7 7 7 5 5 FAN DELA ON 01 1 to 30 seconds Selects time delay for fan ON Applies ...

Page 7: ...nst premature compressor failure by locking out the compressor for at least five minutes after each cycle When the thermo stat is in compressor lockout the word COOL will flash on the display With heat pump systems the word HEAT will flash if the lockout occurs during a heat cycle During this period the compressor will not be energized COMFORT ALERT WITH ACTIVE PROTECTION Installer table step 16 T...

Page 8: ...t service interval SERVICE REMINDER 8 1 Step Press Button s Displayed Press or to select COMMENTS Factory Default PAD TIME OFF Hrs or REM PAD TIME No of Hrs ON or OFF Set Humidifier Maintenance Reminder SERVICE 3 FLTR TIME OFF Hrs or REM FLTR TIME No of Hrs ON or OFF Set Air Filter Maintenance Reminder TIME FWD Service Button Menu Returns to Normal Operation PRGM RUN 2 SET PAD TIME 100 Hrs 25 to 1...

Page 9: ...e and yellow for second stage EMERGENCY heat pump only Press SYSTEM to select EMER mode The LED indicator will glow red for first stage Aux in emergency mode A flashing red LED indicates a malfunction in the system HUMIDIFIER SYSTEM IF INSTALLED 1 Press SYSTEM until HEAT is shown at the top of the display 2 Press the HUMIDITY button once and release Then press the to the maximum humidity setpoint ...

Page 10: ...t does not respond when keys are pressed or the thermostat is not operating properly you may use the reset button located on the back of the thermostat body see fig 2 Thermostat programming and configuration will not be affected by pressing the reset button However the clock will need to be reset RESETTING THERMOSTAT CONFIGURATION AND PROGRAMMING The thermostat can be reset back to default program...

Page 11: ... the size Digital thermostats normally provide precise narrow or wide temperature swing of the Heating System equipment may be temperature control and may cycle faster than influencing the cycle rate someoldermechanicalmodels Afastercycle ratemeanstheunitturnsononoffmorefrequently but runs for a shorter time so there is no increase in energy use If you would like to increase the cycle time refer t...

Page 12: ... will indicate HOLD and the number of hours remaining in the hold period will be indicated with the word HRS To adjust the length of time for the override press TIME FWD or TIME BACK The time you select will become the new number of hours for the Hold Til timing Once your time is selected let the thermostat revert back to normal operation on its own to accept the change Many furnaces have safety d...

Reviews: