background image

 

TLC3-BCR-U Thermostat 

O

PERATION

 

 

Doc: 70-00-0294, V3.1, Date: 20140508 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alteration 

Technical specifications 

Notice!

 Failure to follow specifications and local regulations may cause equipment damage. Misapplication will void 

warranty. 

Power Supply 

Power Requirements  

210 

– 250 V AC 50/60 Hz 

Power Consumption 

Max 1W, 1.5VA 

Electrical Connection 

Terminal Connectors 

Clock backup 

Min 48h if charged for 24h 

Signal inputs 

Temperature Inputs 

Range 
Accuracy 

RT Internal, External (Sxx-Tn10 sensor) 
0…50 °C (32…122 °F) 
0.5°C (1°F) 

Signal outputs 

Digital Switching Outputs 

Switching Type 
AC Switching power 

Insulation strength 

between relays contacts and system electronics: 
between neighboring relays contacts 

Y1 to Y2 
Relays 
0…250V AC 1.25A max. each output 
 
3750V AC to EN 60 730-1 
1250V AC to EN 60 730-1 

Environment 

Operation 
Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0…50 °C (32…122 °F) 
<95 % r.H. non-condensing 

 

Transport & Storage 
Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25

…70 °C (-13…158 °F) 

<95 % r.H. non-condensing 
class 2M2 

Standards 

conformity 
EMC Directive 
Low Voltage Directive 

2004/108/EC 
2006/95/EC 

 

Product standards 

Automatic electrical controls for household and similar use 
Special requirement on temperature dependent controls 

 
EN 60 730 

–1 

EN 60 730 

– 2 - 9 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60 730-1 
Immunity: EN 60 730-1 

 

Degree of Protection 

IP30 to EN 60 529 

 

Pollution Class 

II (EN 60 730-1) 

 

Safety Class 

II (IEC 60536)  

 

Overvoltage Category 

III (EN 60 730-1) 

General 

Dimensions (H x W x D) 

Front part:  
Power case: 

16 x 73 x 113mm (0,7 x 2.9 x 4.5 in.)  
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) 

 

Material:  

Cover, back part 
Mounting Plate 

ABS plastic (UL94 class V-0) 
Galvanized Steel 

 

Weight (including package) 

Standard:  

295g (10.4oz) 

Deluxe (-D):  

305g (10.7oz) 

 

Dimensions, mm (inch) 

  

 

 

Space required in flush mounting box: 

(H x W x D)  
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) 

 

Distance for mounting screws: 

Horizontal 55 to 60mm (2.2 to 2.4 in.)  

Vertical: 55 to 93mm (2.2 to 3.7 in.) 

 

32 (1.3) 

16 (0.7) 

1

1

3

 (

4

.5

73 (2.9) 

Summary of Contents for 40-10 0160

Page 1: ...n General temperature control General TLC3 BCR U 1 independent temperature control loop with 1 heating and 1 cooling sequence 1 internal temperature sensor 1 external temperature input 1 auxiliary inp...

Page 2: ...ng Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards...

Page 3: ...e wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is...

Page 4: ...ints are memorized and do not need to be re entered Upon return of power Set Parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retai...

Page 5: ...to Pro 4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set...

Page 6: ...f inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to...

Page 7: ...rnal temperature sensor 10 to 10 in 0 1 steps Sensor is factory calibrated use this feature for field adjustment only as required 10 10 0 UP 09 Enable Frost Protection Switches to heating mode and act...

Page 8: ...t persist for the length of time set with this parameter before the controller switches Prevents activation of a sequence during a short term change in temperature in order to protect equipment with c...

Page 9: ...alve or damper to the closed position The running time of the actuator may be preset We recommend to enter the maximum running time under maximum load in order to make sure that the valve can fully cl...

Page 10: ...ting X2 input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP17 3 Heat Cool changeover Switch heating and cooling...

Reviews: