TLC3-BCR-U Thermostat 

C

ONTROL 

C

ONFIGURATION

 

 

Doc: 70-00-0294, V3.1, Date: 20140508 

© Vector Controls GmbH, Switzerland 

Page 10 

Subject to alteration 

Input configuration 

Parameter  Description 

Range 

Default 

CP 17 

Changeover input:  

0 = No external input 

1 = Occupation sensor – Comfort / Economy 
2 = Occupation sensor – Comfort / Off 

3 = Heat / Cool change over, heat cool change if over limit 

4 = High / Low limit supervision, outputs switch off if over limit 

0…6 

CP 18 

Activation delay (Minutes) = the time the binary input needs to be 

open before Economy/off mode is activated if CP17 = 1, 2. 
Does not apply for heat cool changeover or high/low limit 

0…255 min 

CP 19 

Heat – cool changeover limit heating if CP17 = 3 
Low limit if CP17 = 4 

-40-60°C 

16°C (61°F) 

CP 20 

Heat – cool changeover limit cooling if CP17 = 3 
High limit if CP17 = 4 

-40-60°C 

28°C (83°F) 

 

 

Configuring the function of the external change over input 

 

CP17 = 0 

CO input not used 

 

CP17 = 1 

Switching Economy and 

Comfort modes 

Economy (unoccupied) and Comfort (occupied) modes are controlled 

through an external contact by connecting X2 through a dry contact to 

signal common. This function may be used together with key card 

switches for hotels or motion detectors for offices.

 

CP17 = 2 

Switching Energy Hold OFF 

and Comfort modes 

Opening the X2 temperature input will force the unit into the OFF 

operation mode. The operation mode cannot be overridden by using the 

terminal. Connecting X2 input to GND returns control of the operation 

mode to the terminal. This function may be used as window contact to 

prevent loss of energy.  

CP17 = 3 

Heat – Cool changeover 

Switch heating and cooling mode based on supply media or outside 
temperature or binary contact. See below for further details.  

CP17 = 4 

High – Low limit 

supervision 

This may be used for a high temperature limit for floor heating or dew 

point sensor input for cooling ceilings. Output will switch off if contact 

opens. 

 

Configuring auto changeover input if CP17 = 3:  

The auto changeover function automatically changes heating and cooling mode based on supply media 

temperature or outdoor temperature. The difference between the two is in the values of the changeover limits 

CP19 and CP20. See table below for recommended settings. 

Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all signal ground 

levels of involved controllers must be the same in case more than one controller is switched.  

 

Recommended settings for CP19 and CP20: 

Change over mode CP17=3 

Relation CP19 to CP20 

Example CP19 

Example: CP20 

Supply media 

CP19 > CP20 

25°C (77F) 

18°C (64F) 

Outside temperature 

CP19 < CP20 

15°C (59F) 

25°C (77F) 

Dry contact: Heating if contact closed 

CP19 > CP20 

25°C (77F) 

15°C (59F) 

Dry contact: Cooling if contact closed 

CP19 < CP20 

15°C (59F) 

25°C (77F) 

 

Change over mode CP17=4 

Relation CP19 to CP20 

Example CP19 

Example: CP20 

Output off if outside range 

CP19 < CP20 

15°C (59F) 

45°C (113F) 

Dry contact: OFF if contact closed 

CP19 < CP20 

-40°C (-40F) 

45°C (59F) 

Dry contact: OFF if contact open 

CP19 < CP20 

15°C (59F) 

80°C (176F) 

 

Summary of Contents for 40-10 0160

Page 1: ...n General temperature control General TLC3 BCR U 1 independent temperature control loop with 1 heating and 1 cooling sequence 1 internal temperature sensor 1 external temperature input 1 auxiliary inp...

Page 2: ...ng Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards...

Page 3: ...e wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is...

Page 4: ...ints are memorized and do not need to be re entered Upon return of power Set Parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retai...

Page 5: ...to Pro 4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set...

Page 6: ...f inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to...

Page 7: ...rnal temperature sensor 10 to 10 in 0 1 steps Sensor is factory calibrated use this feature for field adjustment only as required 10 10 0 UP 09 Enable Frost Protection Switches to heating mode and act...

Page 8: ...t persist for the length of time set with this parameter before the controller switches Prevents activation of a sequence during a short term change in temperature in order to protect equipment with c...

Page 9: ...alve or damper to the closed position The running time of the actuator may be preset We recommend to enter the maximum running time under maximum load in order to make sure that the valve can fully cl...

Page 10: ...ting X2 input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP17 3 Heat Cool changeover Switch heating and cooling...