INSTALLATION
Series 613
76/149
Edition 12.08.2022
984360EC
5.12.9.2
Schematic, Voltage source for digital inputs
5.12.9.3
Digital Input
Pinout
Pin
Default Function
15
INPUT 1
Interlock Close
17
INPUT 2
Interlock Open
23
25
COMMON
COMMON
Switches
Voltage Source
Configuration
Parameter
Description
Enable
1 Enables the input
State
0 Not active
1 Active
Functionality
0 Interlock Open
1 Interlock Close
2 Hold
Inverted
Input State Function
0 Not Inverted
Off
0
Off
On
1
On
1 Inverted
Off
1
On
On
0
Off
The INTERLOCK function has priority over the remote interface (HOLD does not)
INTERLOCK CLOSE has priority over INTERLOCK OPEN