Installation
57
Preparation of electric connection
WARNING
Incorrect installation.
Personal injury and property damage.
The safeguard upstream of the energy
storage system must comply with the
requirements of a circuit breaker.
Secure the device connection at the
energy storage system with a 16A fuse
type B.
Observe the shutdown conditions
according to VDE 0100-410.
Do not connect the energy storage system
without PE and N conductor.
The system is intended for permanent
connection. Neutral and live conductors
must not be mixed up as internal
protective and measuring equipment
would otherwise not work properly.
Between grid and the system, a suitable
circuit breaker (e.g. selective circuit
breaker) must be installed for all-pole
isolation of the system during
maintenance.
Observe the specified line cross-section.
Please note:
For positioning of circuit
breakers, see connection drawings 1a/1b
und 2a/2b in the attachments.
Summary of Contents for Pulse neo Series
Page 1: ...VARTA STORAGE GMBH OPERATING MANUAL VARTA pulse neo...
Page 2: ...Leerseite Pagina vuota Page blanche Blank page...
Page 4: ...Leerseite Pagina vuota Page blanche Blank page...
Page 32: ...General information 32 2 4 2 ID label of battery module 2 4 3 Unlock code label...
Page 64: ...Installation 64 Three Phase Single Phase Not permitted...
Page 67: ...Installation 67 All Dimensions in mm Fig 2 Dimensions at the mounting plate...
Page 145: ...Subject to modification Appendix Appendix 1 Connection diagram of TT system...
Page 146: ...Subject to modification Appendix 2 Connection diagram of TT system with data logger...
Page 147: ...Subject to modification Appendix 3 Connection diagram of TN C system...
Page 148: ...Subject to modification Appendix 4 Connection diagram of TN C system with data logger...