When installing ductings the weight may not be
supported onto the heat pump.
The non-respect of these requirements will be
the reason of warranty exclusion and any cost on
material, animal and personal damages cannot
be forwarded to the manufacturer of this product.
2
1
3
4
4
5
4
1
A
B
C
D
B:
If air inlet is taken from outside and air outlet goes out then
use the VT100C and VT180C as an -10°C unit.
(Solenoid valve, hot gas defrosting mode)
C:
If air inlet is taken from another room and air outlet goes out then
use the VT100C and VT180C as an +5°C unit as long as the ambient
air temperature doesn’t go below +5°C else use an -10°C unit.
(Air / fan defrosting mode only) or
(Solenoid valve, hot gas defrosting mode)
D:
If air inlet is taken from the room and air outlet goes out then
use the VT100C and VT180C as an +5°C unit as long as the ambient
air temperature doesn’t go below +5°C else use an -10°C unit.
(Air / fan defrosting mode only) or
(Solenoid valve, hot gas defrosting mode)
Recommended installation option
By using extracted air make sure a minimum air flow of 100m3/h and
maximum 250m3/h.
If the air inlet temperature will be below +5°C the heat pump must be a
-10°C unit.
ENGLISH
33