SolarCel
Off
This function permits to operate the DHW HP with cheap and environmentally friendly energy from your own solar
cell panels.
“
OFF
” = Solar cells are not connected to system or not chosen to be used by the user.
“
HP only
” , “
EL only
” and “
HP + EL
”: These values indicate the chosen operation mode, when the solar cell
function is activated by the external inverter signal,
see page 19 - Electrical installation for wiring diagram for connection to controller.
SC-HP
52 °C
5°C –
Tmax
Setpoint temperature of “
HP only
“ operating mode, when
Solcel
function activated (inverter signal)
SC-EL
53 °C
5°C –
T max
Setpoint temperature of “
EL only
“ or “
HP + EL
” operating mode, when Solcel function activated (inverter signal)
Holiday
Off
This parameter activates/deactivates the holiday mode. The holiday mode can be selected with the rotary/push
button. The possible selection are:
“
OFF
”, “
1 week
”, “
2 weeks
”, “
3 weeks
”, “
3 days
”, “
Manual
”
When the holiday mode is activated, “
T2 min
” is the safety level for frost protection.
Man.Days
1
This parameter displays the number of holidays at individual (manual) choice. The holiday days can be selected
with the rotary/push button. The possible selection are:
1-99
ReDays
0
This parameter displays status of the remaining number of holidays. The possible values are
0-99
Boost
Off
This parameter activates/deactivates the
BOOST
operating mode in the case of additional need for DHW. If the
BOOST
operating mode is activated “
ON
”, the DHW production will be made by the HP and the supplementary
electrical heating either for a maximum cycle of 1 hour or if
Tmax
is reached. Possible values
“
OFF
”, “
ON
”. The factory setting is “
OFF
”.
FanPause
30m/30s
“
OFF
”, “
30m/15s
”, “
30m/30s
” , “
60m/15s
”, “
60m/30s
” , “
90m/15s
”, “
90m/30s
”
When activated the fan will stop for either 15 or 30 seconds every 30 minutes, 60 minutes or 90 minutes,
according to the selected value.