Due to the high quality of
the insulation you will
experince that the hot water
temperature of 60°C is kept
for more than 1 hour after
the system is switched
back to normal operating
mode. In general 1 hour is
enough to make sure that
all bacterias are gone in the
domestic hot water.
Water
59°C
Status
Le.End
Legionel
Off
Legionel
Manuel
Installers menu:
Press the rotary button until the text flashes and then
rotate the button until “Manuel” appears. Press the
rotary button once and legionella sequence will be
activated for only 1 time cycle.
The heat pump will heat up the water to 60 °C, +-1 °C in
hysteresis by using both the compressor and the
supplementary heating element.
Note!
it is not necessary to switch the heat pump to
“HP + EL” before the electrical heating element can be
used for this function. The software will turn on the
electrical element automatically.
Note!
When activated the lower LED don’t lit up for
showing activation of the supplementary heating element.
User menu:
In the “Water” status menu the user can see
when the 60 °C, +-1 °C in hysteresis has been
reached and the upper LED turns orange for
“standby” mode.
Note!
The legionella software will keep a
surveillance on the temperature for 1 hour* and
then it returns back to normal operating mode
again. This function applies only when the
legionella sequence is activated through the user
menu. The legionella sequence will start
automatically again after 14 days.
User menu:
When the legionella sequence have reached 60 °C, +-1
°C in hysteresis the user can scroll to “Status” menu and
see that the legionella sequence has finished “Le.end”.
This information will stay visible until switching back to
normal operating mode.
Installers menu:
Hold the rotary button for some seconds then you will
go into the installers menu. Rotate the button until the
legionella function appears.
As factory setting the legionella function is set to “OFF”.
ENGLISH
28