ZONE 1 HIGH TEMPERATURE ALARM
This position establishes the temperature
difference
above the main set point (zone 1)
that the room can reach before a high
temperature relative alarm is signalled. When a
high temperature alarm occurs, the alarm relay
is activated and the alarm LED lights up on the
CPS-3M.
The high temperature alarm is adjusted in 0.5
degree increments from a minimum setting of
0.0°F (0.0°C) to a maximum setting of 30.0°F
(18.0°C).
Adjusting the high temperature relative
alarm setting for zone 1:
•
rotate the selector dial to position (12),
•
rapidly rotate the adjustor dial back and
forth to enter secondary function mode,
•
rotate the selector dial to position (9),
•
rotate the adjustor dial counterclockwise to
decrease the setting, and clockwise to
increase it.
The high temperature relative alarm setting is
displayed on the CPS-3M.