ZONE 2 MAXIMUM RUN TIME
The air inlet timer establishes the maximum period
of running time for the actuator’s motor, which
shouldn’t count for more than 25% of the inlet’s
total movement, according to the actuator’s
manufacturer.
The timer is adjusted in 1 second increments from
a minimum setting of 1 second to a maximum
setting of 4 minutes.
Adjusting the inlet timer:
•
rotate the selector dial to position (3),
•
rotate the adjustor dial counterclockwise to
decrease the setting, and clockwise to increase
it.
CHAPTER 3 - USER’S GUIDE
The CPS-3M automatically calculates a run time
according to temperature variations and the difference
between room temperature and the main set point.
Example:
The timer is set to 30 seconds. When the control
determines that the air inlet must open, the timer’s delay
set by primary function (3) must run until the end. Then
the actuator motor will operate for 30 seconds before
stopping.