CPS-3M
HEATING SET POINT
The CPS-3M has an absolute heating set point;
meaning that this function establishes the
temperature at which heating goes ON. It
stops, then starts again when temperature
reaches the heating differential set by position
(7).
When 2 zones are selected, the temperature
considered is the average temperature of the 2
zones. And when only one zone is selected, the
temperature selected is the one in the
controlled zone. For heating to start, the
average temperature of 2 zones or of a single
zone must reach the heating set point.
The heating set point is rounded to the nearest
0.5 degree from a minimum display of 41.0°F
(5.5°C) to a maximum display of 112.0°F (45.0°
C). Upon startup of the heating unit, the
curtains pause for ± 5 second, then close
completely.
Adjusting the heating set point:
•
rotate the selector dial to position (6),
•
rotate the adjustor dial counterclockwise to
decrease the setting, and clockwise to
increase it.
The heating set point is displayed on the CPS-
3M.