ZONE 1 LOW TEMPERATURE ALARM
This position establishes the temperature
difference
below the main set point (zone 1)
that the room can reach before a low
temperature alarm is signalled. When a low
temperature alarm occurs the alarm relay is
activated and the alarm LED lights up on the
CPS-3M.
The low temperature alarm is adjusted in 0.5
degree increments from a minimum setting of -
30.0°F (-18.0°C) to a maximum setting of 0.0°F
(0.0°C)
Adjusting the low temperature relative alarm
setting for zone 1:
•
rotate the selector dial to position (12),
•
rapidly rotate the adjustor dial back and forth to
enter secondary function mode,
•
rotate the selector dial to position (8),
•
rotate the adjustor dial counterclockwise to
decrease the setting, and clockwise to increase
it.
The low temperature relative alarm setting for
zone 1 is displayed on the CPS-3M.
Alarm