REV 3
EZCT S2 USER’S MANUAL
9
3.0 OPERATING
PROCEDURES
3.1
EZCT S2 Cable Connections
Always connect the EZCT S2 to the substation ground before connecting any test cables. The X
cable connections are required to run the current transformer excitation test. The H and X cable
connections are required to run the transformer turns-ratio test. A typical excitation and ratio
test connection is shown in Figure 2. Transformer bushing CT connections for Delta and Y
transformers are shown in Figure 3 and Figure 4, respectively.
Figure 2. Typical EZCT S2 Excitation and Ratio Test Cable Connection