4.4
Normal adventitious ventilation is usually sufficient to satisfy the ventilation
requirements of this appliance. In GB reference should be made to BS 5871 Part 2
and in IE reference should be made to the current edition of IS 813 “Domestic gas
Installations” which makes clear the conditions that must be met to demonstrate that
sufficient ventilation is available
4.5
Note that soft wall coverings (e.g. embossed vinyl, etc.) are easily affected by
heat. They may scorch or become discoloured when close to a heating appliance.
Please bear this in mind when installing.
4.6
The appliance must not be installed in any room, which contains a bath, or
shower or where steam is regularly present.
4.7
The minimum allowable distance from the outside of the appliance fascia to a
corner wall having combustible material or any other combustible surface which
projects beyond the front of the appliance is 100mm at either side (See figure 1). A
clearance of 100mm should be maintained at the right side in all installations to allow
satisfactory access to the control knob. Although no side clearance is necessary to
non-combustible surfaces on the left hand side we recommend a 100mm clearance
for service access to the fascia side fixings.
Page 9
©
Baxi Heating U.K. Limited 2008.
INSTALLER GUIDE
Figure 1. Dimensions and clearances