5.4.2
Wall mounting
(See figure 10).
The closure plate must be fitted and
sealed to the hearth and fireplace
opening using a suitable heat resistant
material
.
If necessary cut the closure plate but
make sure that it overlaps the fireplace
opening sufficiently to allow satisfactory
sealing.
The bottom of the appliance must be at
least 100mm above any carpet or other
floor covering. To achieve this, the bottom
of the flue spigot opening must be at least
565mm above the finished floor covering.
5.4.3
Check the flue pull with closure
plate fitted by applying a lighted match or
smoke match to the flue spigot opening in
the closure plate and observe the smoke.
If there is a definite flow continue with the
installation. If not check the fitting of the
closure plate. The fireplace flue pull check
described in section 5.2 should have
confirmed that the fireplace itself is
satisfactory.