7.1.6
Check all the control settings. These are:-
7.2 Check burner pressure.
The appliance is pre-set to give the correct heat input at the inlet pressure shown in
section 1 of this manual. No adjustment is necessary. Check the burner pressure by
fitting a pressure gauge at the test point. The test point is on the pipe connecting the
gas tap to the lower injector. Check the pressure with the appliance alight and set at
maximum output (Control knob position 4).
After checking, turn off the appliance. Remove the pressure gauge and replace the
test point sealing screw. Relight the appliance. Turn to the maximum output position
and test around the sealing screw for gas soundness with a suitable leak detection
fluid.
If all the above checks are satisfactory, continue with the installation. If not, check the
control and ignition circuitry and components as described in the servicing section of
this manual.
7.3 Test for spillage.
A spillage test must be made before the installed appliance is left with the customer.
7.3.1
Close all doors and windows in the room containing the fire.
7.3.2
Light the appliance and set the control knob to the maximum position (Position
4).
7.3.3
Leave the appliance on for seven minutes.
7.3.4
Insert the smoke match tube (with lighted match) into the side of the appliance
and against the back panel. Position the tube so that it is horizontal, against the back
panel and with its top edge touching the side of the draught diverter box. Slide the
tube until the indent in the tube is level with the diverter side (See figure 13).
7.3.5
The installation is satisfactory if the smoke is drawn into the diverter box. If an
appreciable amount of smoke escapes from above the flue spigot or from the sides
leave the appliance alight at the maximum setting for a further ten minutes and then
repeat the test. If the test is still unsatisfactory disconnect the appliance and seek
expert advice.
7.3.6
If the above test is satisfactory, open all internal connecting doors, hatches, etc.
in the room. Keep all doors and windows that open to the outside of the building
closed. recheck for spillage as above. If an extractor fan is installed in the same room
as the appliance or a connecting room, check that spillage does not occur with the
fan operating and all doors and other openings between the fan and the appliance
open. If the test is satisfactory continue with the installation. If the test is not
Page 20
©
Baxi Heating U.K. Limited 2008.
Control Knob
Position
Burner appearance
1 / IGN
Centre section on low. Outer sections off.
2
Centre section fully on. Outer sections off.
3
Centre section fully on. Outer sections on low.
4
All sections fully on.
INSTALLER GUIDE