Installing the ventilation unit to the
ceiling mounting plate
CAUTION
The ventilation unit is very heavy. Do not perform this
procedure alone.
1. Remove the front panel of the top part of the unit (1)
(leave it hanging from the air flow measuring tubes).
2. Place the connection box cables into the slot in the top
part of the side panel (2) and pull the connection box to
the side of the unit so that the cables remain in the slot.
3. Ensure that the condensing water insulation is in place
in the duct outlets of the extract air duct and of the duct
that comes to the unit from outside.
4. Lift the unit in its place on the ceiling mounting plate
until both locking wings (3) lock on the outer edge of
the side plate of the unit.
5. Visually check the tightness of the duct outlets and the
unobstructed passage of measuring tubes and electric
cables.
6. Put the front panel of the top part back in place.
Attic floor penetration plate
The attic floor penetration plate is optional. When an attic
floor penetration plate is used, the tightness of the vapour
barrier has to be ensured.
MEASURING TUBES
The accessories delivered with the unit include four airflow
measuring tubes. These can be inserted in the ducts to
allow for easier ventilation adjustment.
TIP
You can detach the unit from the ceiling
mounting plate by pulling the spring-loaded
moulding to the direction shown by the
arrow (more detailed information provided
with the ceiling mounting plate).
28
28
38
38
DIMENSIONING OF AND SPACE REQUIRED FOR INSTALLATION OF
THE VALLOX SILENT KLICK WATER SEAL