background image

Fan speed (3).
Supply air temperature (21 

°

C).

Post-heating is on.
Time.
Filter guard alert.

Maintenance reminder alert.
Fireplace / booster switch on. The fireplace /
booster switch is activated in this display by
simultaneously pressing down the + and – buttons
for 2 seconds.
Week clock control on.

21 C

10:20

1

2

3

4

5

6

7

8

VALLOX DIGIT SE/SE VKL

INSTRUCTIONS FOR USING THE CONTROL PANEL

8

© VALLOX • We reserve the right to make changes without prior notification.

3.2. 

Operating menu

In order to move the control panel to the settings menu, press the + and – buttons simultaneously.
In the settings menu, you can change setpoints for the ventilation unit.

The content display shows humidity and carbon dioxide content. The corresponding
sensors are required (options).

The temperature display shows the temperatures of outdoor air, indoor air, supply air
and exhaust air. The accuracy of the temperature sensors is 

±

 2 

°

C.

Supply air temperature setting is changed with the + and – buttons.

3.2.1.  Main display and change of fan speed

3.2.2.  Moving to the settings menu

3.2.4.  Content display

3.2.5. Temperature 

display

3.2.6.  Setting supply air temperature

Fan speed can be changed in this display with the + and – buttons
(see section 3.1., items 7 and 8 in the figure).

The displays of the operating menu (sections 3.2.1.–3.2.6.) can be scrolled with the scrolling buttons
(see section 3.1., items 5 and 6 in the figure).

To settings menu
See manual

RH1 35%     RH2   40%
CO2           0821  PPM

Out 20 

In 20

Sup. 20 

Exh. 20

Temp. setting
20C

5

Scrolling up

With this button, you can scroll the displays upward.

6

Scrolling down

With this button, you can scroll the displays downward.

7

Increase button

With this button, you can increase values.

8

Decrease button

With this button, you can decrease values.

2

Carbon dioxide adjustment

With this button, you set carbon dioxide
adjustment on and off. When the indicator is
lit, the adjustment is on.

3

Humidity adjustment

With this button, you set humidity adjustment
on and off. When the indicator is lit, the
adjustment is on.

4

Post-heating

With this button, you set post-heating on and
off. When the indicator is lit, post-heating is on.
The summer function is active when the indicator
is not lit.

3.1. Keyboard

Power failure

After a power failure, the unit starts at minimum
fan speed. The adjustments and setpoints chosen
will remain in the memory of the unit in spite of
the power failure.

3.

Control panel

1

Start button

With this button, you switch the unit on and off.
When the indicator is lit, the unit is on.

3

21 C

3

10:20

Week clock control can be activated by pressing the + button and deactivated by pressing the –
button. Week clock control is on when the symbol of week clock control is shown in the main
display. In week clock control, the basic fan speed and supply air temperature of the unit are
adjusted in accordance with the programme in section 3.3.4.

3.2.3.  Week clock control

Week program
on

Summary of Contents for DIGIT SE

Page 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Page 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Page 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Page 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Page 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Page 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Page 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Page 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Page 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Page 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Page 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Page 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Page 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Page 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Page 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Page 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...