TROUBLESHOOTING

VALLOX DIGIT SE/SE VKL

© VALLOX • We reserve the right to make changes without prior notification.

Outdoor air coming to
the dwelling is cold.

SYMPTOM

REASON

DO THIS

• Air cools down in the attic ducts.

• The heat recovery cell is frozen, which is

why extract air cannot heat outdoor air.

• The post-heating radiator does not work.

• The extract air filter or the cell is clogged.

• The initial adjustment of ventilation has not

been done.

1

• Check the insulation of the attic ducts.

• If the heat recovery cell is frozen, check the setpoint for

freezing protection. The setpoint for freezing protection can
be raised by 1 or 2

°

C, or the sensor can be bent closer to

the cell, in which case the supply air fan stops earlier (see
the instructions for using the control panel in Section
3.3.23.). Thaw the cell before closing the door.

• If the post-heating radiator does not operate, check to see if

overheating protection prevents it from operating. Press the
overheating protection reset button (see page 14, Q), and
measure the temperature of supply air inside the unit when
the door is closed. If the radiator does still not work, contact
a maintenance company.

• Check that the filters and the heat recovery cell are clean.

Supply air fan keeps stopping

• HR cell antifreeze is in operation.

NOTE! If you decrease the setpoint too much, the
cell may freeze. Compare with list item 1.

2

• The fan stops more rarely and the efficiency of the heat

recovery cell gets better when the setpoint is decreased by
1 or 2 

°

C. (See the instructions for using the control panel,

Section 3.3.23.)

Supply air fan stops and
starts too frequently.

• The difference between the stopping and

starting temperatures is too small.

• The preheating radiator does not work.

3

• Raise the difference between the stopping and starting tem-

peratures by 1 or 2 

°

C. It extends the period between stop-

ping and starting. (See the instructions for using the control
panel, Section 3.3.22.)

• If the preheating radiator does not operate, check if over-

heating protection prevents it from operating: press the
overheating protection reset button, and measure the tempe-
rature of outdoor air inside the unit before the heat recovery
cell when the door is closed. If the radiator does still not
work, contact a maintenance company.

The maintenance reminder
symbol ( ) is displayed and
the unit operates otherwise
normally.

• The maintenance reminder lights up the

service reminder symbol in the main
display of the control panel at an interval
of approximately 4 months (factory
setting).

• You may change the interval (see the

instructions for using the control panel,
Section 3.3.21.).

4

• Check the cleanliness of the filters and the unit. If needed,

clean or replace the filters. Also check the external grille.

• Reset the maintenance reminder symbol to make it

disappear. (See the instructions for using the control panel,
Section 3.3.10.)

"Exh air sensor faulty"
message is displayed and
the unit is stopped.

• There is a fault in the freezing protection

sensor.

5

• Contact a maintenance company. Sensor mounting needs to

be checked and the sensor has to be replaced if necessary.

"Sup. air sensor faulty"
message is displayed and the
unit is stopped.

• There is a fault in the supply air sensor.

6

• Contact a maintenance company. Sensor mounting needs to

be checked and the sensor has to be replaced if necessary.

"Inp. air sensor faulty"
message is displayed and the
unit is stopped.

• There is a fault in the extract air sensor.

7

• Contact a maintenance company. Sensor mounting needs to

be checked and the sensor has to be replaced if necessary.

"Out air sensor faulty"
message is displayed and the
unit is stopped.

• There is a fault in the outdoor air sensor.

8

• Contact a maintenance company. Sensor mounting needs to

be checked and the sensor has to be replaced if necessary.

Summary of Contents for DIGIT SE

Page 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Page 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Page 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Page 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Page 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Page 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Page 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Page 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Page 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Page 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Page 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Page 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Page 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Page 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Page 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Page 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Reviews: