11

INSTRUCTIONS FOR USING THE CONTROL PANEL

© VALLOX • We reserve the right to make changes without prior notification.

3.4. Week clock control

The week programme can be used to set the desired fan speed (basic fan speed) and supply air
temperature for each hour of the day on seven days a week. The week programme overrides
manual adjustments.
Carbon dioxide and humidity adjustment can increase fan speed but never decrease it below the
basic fan speed set in the week programme.

3.4.1.

Week programme programming

D

Hr

Sp

Tmp

1

12

5

20

Exit

Cursor

D  

Day 1…7
1 = Monday, 2 = Tuesday, etc.

Hr   Hours, 0…23
Sp   Fan speed, 1…8
Tmp   Supply air temperature, 10...30 ºC
Exit   Save the setting and exit
N  

No change to previous

Example: Monday

Fan speed is increased to speed 2 and supply air temperature to 17 ºC between 07:00 (7 a.m.)
and 17:00 (5 p.m.) hours. After that, fan speed is raised to speed 4 and supply air temperature to
20 ºC. For the evening, fan speed is boosted to speed 6 between 19:00 and 21:00 hours (for the
period when a sauna bath is taken), after which fan speed is lowered back to 4.
Move the cursor with the arrow keys and change values with the + and – buttons. Note that Exit
and saving are done when the programming is finished by moving the cursor below the word Exit
and pr or –.

Changes in fan speed (Sp) and supply air temperature (Tmp) are only made for the hours desired;
in other cases, use N (no change to previous).

Monday (D = 1), 07:00 hours (H = 7), fan speed 2 (Sp = 2), supply air temperature 17 ºC (Tmp =
17). Move the cursor to the following hour.

Monday (D = 1), 16:00 hours (H = 16), fan speed 4 (Sp = 4), supply air temperature 20 ºC (Tmp
= 20). Move the cursor to the following hour.

Monday (D = 1), 19:00 hours (H = 19), fan speed 6 (Sp = 6), supply air temperature unchanged
(Tmp = N). Move the cursor to the following hour.

Monday (D = 1), 21:00 hours (H = 21), fan speed 4 (Sp = 4), supply air temperature unchanged
(Tmp = N). Move the cursor to the following day.
Similar changes have to be made separately for each day. Finally, exit the programming mode by
selecting Exit. If you wish, you can erase the week programme as indicated in section 3.3.3. You
can then start programming from the start. You can see the settings programmed by choosing a day
and by scrolling the hours with the + or – button.

D

Hr

Sp

Tmp

1

7

2

17

Exit

D

Hr

Sp

Tmp

1

16

4

20

Exit

D

Hr

Sp

Tmp

1

19

6

N

Exit

D

Hr

Sp

Tmp

1

21

4

N

Exit

Move the cursor with the arrow keys and change values with the + and – buttons. Exit
and saving are done when the programming is finished.
Monday (D = 1), hours 15 (H = 15), minutes (M = 30).
Time is maintained even though there is a power failure.

3.4.2. Adjusting 

time

day hour

min

1

15

30

Exit

day   Day 1…7

1 = Monday, 2 = Tuesday, etc.

hour   Hours, 0…23.
min   Minutes 0…60
Exit   Save the setting and exit

Cursor

Summary of Contents for DIGIT SE

Page 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Page 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Page 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Page 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Page 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Page 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Page 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Page 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Page 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Page 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Page 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Page 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Page 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Page 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Page 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Page 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Reviews: