"Bus fault" message is
displayed and the unit
operates at speed 1
(check the fan speed).

• Wiring fault in the carbon dioxide sensor,

in the control panel or in the humidity
sensor.

9

• Contact a maintenance company. The connections have

to be checked and corrected if necessary.

"Freezing alert" message
is displayed and the unit is
stopped.

• Antifreeze of the water-circulating radiator

is active.

NOTE! If there is no non-freezing solution in the
water of the radiator, the radiator is at risk of
freezing.

10

• Immediately troubleshoot the situation. Consult a

maintenance company to find out if there is any non-
freezing solution in the radiator. Check if the circulation
pump is broken, the boiler out of operation etc. The
situation may pass by itself as soon as supply air
temperature exceeds 10 degrees, but do not wait till it
happens.

The desired automatic
adjustment does not stay
on.

• There is a fault in the humidity or carbon

dioxide sensor. One of the sensors is
broken or missing.

11

• Contact a maintenance company. The sensor installation

and connections have to be checked. (The sensors are
optional.)

The unit does not work,
the fans are not running
and no indicator light is lit
in the control panel.

• The door switch may be broken, or the

door is possibly not quite closed.

• The unit is out of power, e.g. because a

fuse has blown.

• The glass tube fuse (located in the control

card behind a protecting plate) the
electronics inside the unit may have blown.

12

• Check the door switch and fuses. The unit includes a

T800 mA glass tube fuse.

• If needed, contact a maintenance company (e.g. to

check the glass tube fuse).

The unit does not obey
the control panel.

13

• Remove the plug from the wall outlet, wait for 30

secondsand put it back. If this does not help, contact a
service representative.

"Carbon dioxide alarm"
message is displayed and
the unit is stopped.

• Carbon dioxide alarm. Carbon dioxide

content has exceeded 5000 PPM for two
minutes. May be caused by a fire.

14

• If there is a fire, take the necessary steps.

• You can make the unit operative by disconnecting the

plug from the wall socket, waiting for 30 seconds and
putting the plug back again.

• Check the cleanliness of the filters and the unit. If needed,

clean or replace the filters. Also check the external grille.

15

The filter guard symbol
( ) is displayed and the
unit operates otherwise
normally.

• The pressure in the filter guard (pressure

difference switch) has risen above the
adjustment value or speed is 7 or 8.

SYMPTOM

REASON

DO THIS

© VALLOX • We reserve the right to make changes without prior notification.

1.09.61E/27.5.2008/PDF

VALLOX DIGIT SE/SE VKL

Vallox Oy FIN-32200 Loimaa Finland Tel358 2 7636 300 Fax +358 2 7631 539

Internet: www.vallox.com.

TROUBLESHOOTING

After a power failure, the unit starts at minimum fan speed.
All the other selected adjustments and setpoints remain in the memory of the unit.

Summary of Contents for DIGIT SE

Page 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Page 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Page 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Page 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Page 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Page 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Page 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Page 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Page 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Page 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Page 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Page 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Page 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Page 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Page 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Page 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Reviews: