2.9. Supply air constant temperature control

• In DIGIT SE, post-heating control is proportional: when the chosen temperature exceeds

supply air temperature by more than 2.5

°

C, the radiator is on 100% of the time; when the

temperature differential gets smaller, the on time of the radiator is reduced automatically in
two-minute sequences. The temperature range is 10…30

°

C.

• The heating radiator is on when the  -sign is displayed.
• Temperature control is only active when post-heating has been switched on.

2.10. Supply air cascade control

• Supply air temperature control can be replaced with cascade control.
• Cascade control changes the mode of regulating the post-heating radiator: the temperature of

air blown to the ventilation zone is controlled on the basis of extract air.

• The program aims at keeping supply air temperature at the value that depends on the

difference between extract air and the setpoint as follows: if extract air is hotter than the
setpoint, the temperature of supply air is lower than the setpoint by the same amount. If extract
air is cooler than the setpoint, supply air is hotter by the same amount. For instance, if indoor
air temperature is 25

°

C and the setpoint is 24

°

C, the aim is to blow 23

°

C air to the ventilation

zone. If the temperature in the ventilation zone is 24

°

C and the setpoint is 25

°

C, the aim is to

blow 26

°

C air to the ventilation zone.

• The aim is to permanently keep the temperature of air blown to the ventilation zone within the

range 10...30 

°

C.

• Cascade control can be chosen on the control panel, and it is active when post-heating has

been switched on.

• The heating radiator is on when the  -sign is displayed.

2.11. Heat recovery bypass

• The aim of the heat recovery bypass function is to ensure that supply air coming to the

ventilation zone is as cool as possible. To do this, the heat recovery bypass function compares
the measurement data of the outdoor and extract air sensors.

• The heat recovery cell is bypassed, when the post-heating function is off, when outdoor air

temperature exceeds two degrees the setpoint and when extract air is hotter than outdoor air.

• The setpoint can be changed between 0…+25

°

C. (Factory setting 10

°

C).

2.12. Heat recovery defrost function and preheating

• Defrost prevents the heat recovery cell from freezing, thus ensuring proper ventilation even in

cold periods.

• In a standard ventilation unit, defrosting is implemented by intermittently stopping the supply

air fan. The stopping function is controlled on the basis of the measurement data given by the
temperature sensor that measures the temperature of exhaust air after the heat recovery cell.

• The supply air fan stops when exhaust air temperature falls to the setpoint (factory setting

+4

°

C) and starts when exhaust air temperature has risen to the value set (hysteresis setting,

factory s3

°

C).

Preheating

• The system can also be equipped with an optional preheating facility. The preheating radiator

(A) has been installed in the outdoor air duct (B). It is switched on before the supply air fan
stops. The operation is controlled by the same sensor that has been installed in exhaust air.
The heater is switched on at a temperature higher than the stopping temperature (factory
s6

°

C). If preheating cannot keep exhaust air temperature warmer than the stopping

temperature, the outdoor air fan stops. When the risk of freezing has passed, preheating is
switched off and the supply air fan starts automatically.

• Post-heating is on throughout the freezing risk period.

2.13. Maintenance reminder

• The maintenance reminder switches on the maintenance reminder symbol ( ) in the main

display of the control panel at defined intervals, the factory setting being 4 months.

• The maintenance reminder symbol is acknowledged at the control panel (see the instructions

for using the control panel, Section 3.3.10.).

• The interval can be set between 1...15 months at the control panel.

A

B

© VALLOX • We reserve the right to make changes without prior notification.

Preheating

Summary of Contents for DIGIT SE

Page 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Page 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Page 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Page 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Page 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Page 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Page 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Page 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Page 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Page 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Page 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Page 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Page 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Page 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Page 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Page 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Reviews: