2.4. Ventilation control with carbon dioxide sensor (option)

• In carbon dioxide control, DIGIT SE adjusts fan speed so as to keep the carbon dioxide

content in the ventilation zone below the setpoint. If two or more sensors are used, fan
speed is adjusted in accordance with the highest measuring result.

• 1...5 optional carbon dioxide sensors may be connected to the VALLOX DIGIT SE unit.
• The adjustment is switched on / off and, if needed, the setpoint (500...2000 ppm) is

defined on the control panel. The factory setting is 900 ppm. The maximum carbon dioxide
content of indoor air should be 1000 ppm.

• While control is activated, you can use the control panel to raise fan speed to the maximum

speed and to lower it to the basic fan speed. In carbon dioxide control, maximum fan speed
limitation is enabled.

2.5. Ventilation control with humidity sensor (option)

Fan speed can be controlled in two ways:
1 Automatic humidity setting. This is suitable for controlling the washrooms in residential

buildings, for instance. The program records the current humidity level and defines it as the
setpoint used as the target value for making air dry after a shower, for instance. The setpoint
changes automatically according to season, and is always correct. This is the factory
setting.

2 You can also set a fixed humidity level of 1…99 %RH on the control panel. This setting can

be used in public saunas and public swimming pools. The program aims at maintaining
humidity at the chosen value. The setpoint can be changed as needed.

The mode of regulation is selected on the controller. The relative humidity of indoor air should
preferably be about 45%.
• While control is activated, you can use the control panel to raise fan speed to the maximum

speed and to lower it to the basic fan speed.

• In humidity control, the fan speed varies between the basic and maximum fan speeds set.
• When the unit is taken into use for the first time, with automatic setpoint search selected

(factory setting), it will take the program 3...10 hours to determine the value. During this
time, humidity control is not active (because the first value set at the factory is 100%).

• Automatic search is active, even if humidity control has not been selected.

2.6. Ventilation control with voltage or current signals

• The fan speeds of DIGIT SE can be controlled with voltage or current signals coming from

the remote monitoring system.

• The signal can be used to select speeds 0...8. However, the maximum fan speed may not

be exceeded if carbon dioxide or humidity control is active.

• The signal changes the basic fan speed.
• The signal does not lock the fan speed, i.e. it can be changed on the control panel within

the defined range. Carbon dioxide and humidity controls also operate within the defined
range.

2.7. Ventilation control with remote monitoring system (option)

• With the help of an optional LON converter, DIGIT SE can be connected to a remote

monitoring system.

• Before connecting DIGIT SE to the remote monitoring system, make sure that they are

compatible.

• The remote monitoring system may be used to control the same functions as on the control

panel.

• The remote monitoring system works in parallel with the control panel and the carbon

dioxide and humidity sensors.

2.8. Post-heating

For most of the year, the heat recovered from air to be extracted is enough to heat the cool air
coming from outside to a suitable temperature. If the heat of extract air is not enough, the air
coming from outside can be heated with the radiator included in the unit. The post-heating
radiator may be electric or water circulated. In both cases, heating can be activated on the
control panel (see section 3.1. of the instructions for use). When heating has been activated,
the unit automatically sets the temperature selected.

Carbon dioxide (CO

2

) sensor

Humidity (RH) sensor

2.8.

LON converter

© VALLOX • We reserve the right to make changes without prior notification.

Summary of Contents for DIGIT SE

Page 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Page 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Page 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Page 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Page 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Page 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Page 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Page 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Page 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Page 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Page 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Page 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Page 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Page 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Page 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Page 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Reviews: