56
WALL MOUNTING
Note the following before mounting:
•
Mount the Vallox 096 MV / 110 MV in a place where the
temperature does not fall below +10°C.
•
Avoid mounting the unit on a hollow, echoing partition wall or
on a bedroom wall, or prevent the conduction of sound.
•
The minimum distance between the top of the unit and the
finished ceiling surface is 30 mm. Note that during mounting
the unit rises 10 mm higher than the final height.
•
Without protective closure, the unit must be located in a
place where the noise does not disturb anyone (storage,
technical rooms, etc.).
Mount the Vallox 096 MV / 110 MV on the wall with a mounting
plate, as shown in the adjacent figure. Make sure that the unit is
horizontally level after mounting.
MEASURING TUBES
The accessories delivered with the unit include four airflow
measuring tubes. These can be inserted in the ducts to allow for
easier ventilation adjustment.
NOTE
Mount 145 MV on the floor rack, or on the wall with a mounting
plate.
CEILING MOUNTING BY USING THE CEILING
MOUNTING PLATE
Models 096 MV and 110 MV can be equipped with an optional
ceiling mount plate. Attach the ceiling mounting plate:
•
To the ceiling with M8 thread bars so that they stand the
weight of the unit.
•
Horizontally to make sure the unit is horizontally level.
Insulate the outdoor air and exhaust air duct against condensation
also between the unit and the ceiling mounting plate.
INSTALLATION
INST
ALLA
TION