Single & Dual Zone Heat Trace Control Panel | Valin Corporation
FIG. 2-1 VERTICAL
MOUNTING ONLY
8
INSTALLATION
WARNING!
AccuTrace™ utilizes Solid State
Relay (SSR) power switching. To dissipate the
heat generated from the SSR’s, the heat sink
located on the back of the enclosure must
be in an upright position. The panel must be mounted
vertically as shown below in Figure 2-1 to accomplish
proper heat dissipation.
WARNING!
Installation of equipment must
be performed by qualified and experienced
personnel.
Mounting Location
Determine the mounting location based upon the
enclosure dimensions shown in the Overview Section.
If installed indoors the recommended materials include
metal surfaces, concrete, or wood. If mounting on drywall,
the construction requirements must be of at least ½”
thickness, supported by 2”x4” studs on 16” centers. If
installed outdoors, metals must be corrosion resistant
and woods must be sealed and treated for outdoor use.
Anchors must be capable of supporting at least 100lbs
each.