Single & Dual Zone Heat Trace Control Panel | Valin Corporation
COMMUNICATIONS
FIGURE 5-8 CIRCUIT 2 INTEGER VALUES
Parameter Name
Description
Range
Modbus Address
Data Type
Access
Circuit 2 Temperature SP
Temperature setpoint of Circuit 2
0-720˚F
400201
Unit
Read Only
Circuit 2 Mode
View control mode of Circuit 2
0-3
400202
Unit
Read Only
Circuit 2 Man Mode Power
Power output (%) for Circuit 2
0-100%
400203
Unit
Read Only
Circuit 2 On/Off Mode DB+
Circuit 2 Deadband high
range temperature
0-100°F
400204
Unit
Read Only
Circuit 2 On/Off Mode DB-
Circuit 2 Deadband low
range temperature
0-100°F
400205
Unit
Read Only
Circuit 2 High Current Alarm SP
Set point for High
Current Alarm Circuit 2
1-40 and > than
low alarm
400206
Unit
Read Only
Circuit 2 Low Current Alarm SP
Set point for Low
Current Alarm Circuit 2
1-40 and < than
high alarm
400207
Unit
Read Only
Circuit 2 High Temp Alarm SP
Set point for High Temp
Alarm Circuit 2
0-720 and >
than low alarm
400208
Unit
Read Only
Circuit 2 Low Temp Alarm SP
Set point for Low Temp
Alarm Circuit 2
0-720 and < than
high alarm
400209
Unit
Read Only
Circuit 2 GFEP SP
Set point for High GFEP
Alarm Circuit 2
20-80mA
400210
Unit
Read Only
Circuit 2 High Current
Alarm Time Delay
Set time delay for Circuit
2 High Current Alarm
500-60000msec
400211
Unit
Read Only
Circuit 2 Low Current
Alarm Time Delay
Set time delay for Circuit
2 Low Current Alarm
500-60000msec
400212
Unit
Read Only
Circuit 2 High Tempera-
ture Alarm Time Delay
Set time delay for
Circuit 1 High Temp Alarm
500-60000msec
400213
Unit
Read Only
Circuit 2 Low Tempera-
ture Alarm Time Delay
Set time delay for
Circuit 2 Low Temp Alarm
500-60000msec
400214
Unit
Read Only
Circuit 2 GFEP Alarm Time Delay
Set time delay for
Circuit 2 High GFEP Alarm
500-60000msec
400215
Unit
Read Only
Circuit 2 GFEP Auto
Test Cycle Time
Set the Cycle Time for GFEP
Auto Test on Circuit 2
400216
Unit
Read Only
Circuit 2 Proportional Gain
Enter value for
Proportional Gain (Kp) Circuit 2
1-1000
400217
Unit
Read Only
Circuit 2 Integral Factor
Enter value for
Integration Factor (Ti) Circuit2
0-100
400218
Unit
Read Only
Circuit 2 Derivative Factor
Enter value for
Derivation Factor (Td) Circuit 1
0-50
400219
Unit
Read Only
59