Single & Dual Zone Heat Trace Control Panel | Valin Corporation
PRESS THE “LOG-IN” BUTTON
ON THE HOME SCREEN
PRESS
“MENU”
PRESS
“SYSTEM
SETTINGS”
PRESS
“MODES”
ENTER YOUR PASSWORD AND PRESS THE “LOG-
IN” BUTTON NEXT TO THE ENTRY FIELD
SET UP
ACCUTRACE™ QUICK START GUIDE
Step 1. Log in (Figures 3-3 – 3-6 for more info)
Step 2. Modes Menu (Figure 4-1 for more info)
Step 3. Select a Control Mode
(Figure 4-6 for more info)
Auto PID
- A closed loop control method
that will control the power output based
on a PID algorithm. The variables can be
modified from the
System Settings Menu
under
PID Settings
.
Manual
- An open loop control method that
sets the power output to a user-specified
percentage. Manual Mode is also the
failover mode from Auto PID or On/Off
when the temperature sensor fails. Set
the output accordingly for the application
range of power limit (%).
On/Off
- A closed loop control method
that utilizes Deadband hysteresis values
to determine the power output. The output
will turn off once the process temperature
reaches the deadband’s high setpoint and
turns on when the process temperature
reaches the deadband’s low setpoint.
Step 4. Enable the Circuit!
You have completed your Quick Set Up!
Press the “HOME” button to view your
process.